G9SP
Application Templates
Emergency Stop Pushbutton Application
PL/Safety Category
PLe/4 equivalent
Application Overview
The power supply to motor M is turned OFF when emergency stop switch S1 is pressed.
Wiring Example
Timing Chart
Reset ON
E-STOP pushed
E-STOP S1
11-12
E-STOP S1
21-22
More than
350 ms
Reset S2
KM1
KM2
EDM
feedback
Program
Model
Emergency stop pushbutton
Discrepancy error
Discrepancy
E-STOP released
error released
More than
More than
350 ms
350 ms
EDM error
Stop category
A165E/A22E
E1 and E2:
S1:
S2:
KM1 and KM2: Contactors
M:
Note: Refer to page 20 for the terminal arrangement.
Safety I/O Terminal Settings
Input Terminals
EDM error released
Output Terminals
Precautions for Safe Use
• Perform a function test every six months to
detect contact welding failures on contactors.
• It is the user's responsibility to make sure that
the entire system complies with standards.
• For safety reasons, two electrical switching
elements and two relays or contactors are
always necessary to detect electrical faults and
mechanical faults.
Reset
0
Manual
24-VDC power supplies
Emergency stop switch
Reset switch
Motor
11