Table 12 Electrical Specifications W**Ab - Bard 11EER WA Series Installation Instructions Manual

Wall mount air conditioner
Table of Contents

Advertisement

Rated
Model
Volts
& Phase
W18AB-A00, A0Z
A05
230/208-1
A08
A10
W24AB-A00, A0Z
A05
230/208-1
A08
A10
W24AB-B00, B0Z
230/208-3
B06
W24AB-C00, C0Z
460-3
C06
W30AB-A00, A0Z
A05
A08
230/208-1
A10
A15
W30AB-B00, B0Z
B06
230/208-3
B09
B15
W30AB-C00, C0Z
C06
C09
460-3
C12
C15
W36AB-A00, A0Z
A05
A08
230/208-1
A10
A15
W36AB-B00, B0Z
B06
230/208-3
B09
B15
W36AB-C00, C0Z
C06
460-3
C09
C15
 These "Minimum Circuit Ampacity" values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest
version), Article 310 for power conductor sizing. CAUTION: When more than one field power circuit is run through one conduit, the
conductors must be derated. Pay special attention to note 8 of Table 310 regarding Ampacity Adjustment Factors when more than
three (3) current carrying conductors are in a raceway.
 Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.
 Based on 75°copper wire. All wiring must conform to the National Electrical Code and all local codes.
NOTE: The Maximum Overcurrent Protection (MOCP) value listed is the maximum value as per UL 1995 calculations for MOCP (branch-
circuit conductor sizes in this chart are based on this MOCP). The actual factory-installed overcurrent protective device (circuit
breaker) in this model may be lower than the maximum UL 1995 allowable MOCP value, but still above the UL 1995 minimum
calculated value or Minimum Circuit Ampacity (MCA) listed.
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor
wires in accordance with the National Electrical Code and all local codes.
Manual 2100-689H
Page
30 of 42
TABLE 12
Electrical Specifications − W**AB Series
Single Circuit
No.
Field
Maximum
Minimum
Power
External
Circuit
Circuits
Fuse or
Ampacity
Ckt. Brkr.
1
16
20
1
30
30
1
45
45
1
56
60
1
21
25
1
30
30
1
46
50
1
57
60
1
15
20
1
23
25
1
8
15
1
12
15
1
23
35
1
31
35
1
47
50
1
57
60
1 or 2
83
90
1
17
20
1
23
25
1
32
35
1
50
50
1
9
15
1
12
15
1
16
20
1
21
25
1
25
25
1
27
35
1
32
35
1
48
50
1
58
60
1 or 2
84
90
1
20
25
1
24
25
1
33
35
1
51
60
1
11
15
1
12
15
1
17
20
1
26
30
Minimum
Field
Circuit
Power
Ground
Ampacity
Wire
Wire
Size
Ckt.
Ckt.
A
B
12
12
10
10
8
10
6
10
10
10
10
10
8
10
6
10
12
12
10
10
14
14
14
14
8
10
8
10
8
10
6
10
4
8
57
26
12
12
10
10
8
10
8
10
14
14
14
14
12
12
10
10
10
10
8
10
8
10
8
10
6
10
4
8
58
26
10
10
10
10
8
10
6
10
14
14
14
14
14
14
12
12
Multiple Circuit
Maximum
External Fuse
Field Power
or
Wire Size
Wire Size
Ckt. Breaker
Ckt.
Ckt.
Ckt.
Ckt.
Ckt.
A
B
A
B
60
30
6
10
10
60
30
6
10
10
Ground
Ckt.
A
B
10
10