2.3 - Operating limits

Cooling mode:
Supply air temperature 12°C, when the unit is installed in
an ambient temperature of 27°C dry bulb and 65% relative
humidity.
Heating mode:
The air discharge temperature must not exceed 60°C to
avoid damage of the discharge spigots.
To avoid the risk of stratification and the resulting discom-
fort, Carrier advises to keep the discharge temperature
below 35°C.
Operating environment
The 42EM Atmosphera has been designed for internal
application in "urban" conditions having a non-corrosive,
dust free and non-marine environment.
The concentrations of the following chemicals must not
be exceeded in any event:
SO
< 0,02 ppm
2
H
S
< 0.02 ppm
2
NO, NO
< 1 ppm
2
NH
< 6 ppm
3
N
O
< 0.25 ppm
2
Recommended coil water quality
At installation handover, and then periodically every year, it is
advised to analyse the water for bacteria (detection of ferro-
bacterias, H
S producing and sulphate reducing bacteria) and
2
chemicals (in order to avoid problems due to corrosion and
scaling).
The water circuit must include all the necessary elements for
the treatment of the water: filters, additives, intermediate
exchangers, purges, drains, isolating valves, etc., according to
the analysis results.
The results must be in accordance with the values shown below:
Total hardness in French degrees:
Chloride [CL
-
]
Sulphate [SO
2-
]
4
Nitrate [NO
-
]
3
Dissolved iron
Dissolved oxygen
Carbon dioxide [CO
Resistivity
pH
10 < TH < 15
< 10 mg/l
< 30 mg/l
= 0 mg/l
< 0.5 mg/l
4 < [O
] < 9 mg/l
2
]
< 30 mg/l
2
2000<Resistivity
<5000 Ωcm
6.9 < pH < 8
7