Error Code And Trouble Shooting; Overload Of Compressor Or Fan In #2 - Daikin UHA075B5 Catalogue/Engineering Data

Modular air source heat pump water heater
Table of Contents

Advertisement

Error Code and Trouble Shooting

Error code on wired controller
When the unit has failure alarm, wired controller will display the error code.
Alarm display has two parts, A is error code, B is unit number.
If the unit has 2-way valve interlocking function on, when the unit interlocked by 2-way valve, wired controller
display "SA".
S/N
Code
1
F6
2
01~15
3
16
4
17
5
18
6
19
7
20
8
21
9
22
10
23
11
24
12
25
13
26
14
27
15
28
16
29
17
30
18
31
19
32
20
33
21
34
22
35
23
36
46
Symptoms
Communication failure with master unit
1# ~15# slave communication failure
Overload of compressor or fan in #1

Overload of compressor or fan in #2

Overload of pump
Lack of water flow
High pressure of #1
Low pressure of #1
Dicharge superheat of #1 is too low
Dicharge superheat of #2 is too low
High pressure of #1
Reserved
Overload of water system heater
Ambient temperature too high/low
Reserved
Superheat of #1 is too low
Reserved
Communication failure with master unit
Suction temperature #1 is too high
Discharge temperature #1 is too high
Suction temperature #2 is too high
Discharge temperature #2 is too high
Low pressure of #2
S/N
Code
24
37
Superheat of #2 is too low
25
38
Refrigerant leakage in #1
26
39
Refrigerant leakage in #2
TH1 temperature sensor
27
40
malfunction
TH2 temperature sensor
28
41
malfunction
TH3 temperature sensor
29
42
malfunction
TH4 temperature sensor
30
43
malfunction
TH5 temperature sensor
31
44
malfunction
TH6 temperature sensor
32
45
malfunction
TH7 temperature sensor
33
46
malfunction
TH8 temperature sensor
34
47
malfunction
TH9 temperature sensor
35
48
malfunction
TH10 temperature sensor
36
49
malfunction
TH11 temperature sensor
37
50
malfunction
TH12 temperature sensor
38
51
malfunction
Low pressure sensor malfunction
39
52
of #2
Low pressure sensor malfunction
40
53
of #1
41
54
Memory failure
Water tank temperature too high/
42
55
low
43
56
Water level switch malfunction
44
57
EWT/LWT too high
45
58
Anti-freezing protection
46
60
No system can start up
Symptoms

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Uha100b5Uha200b5

Table of Contents