Specifications - Daikin UHA075B5 Catalogue/Engineering Data

Modular air source heat pump water heater
Table of Contents

Advertisement

Specifications

General data
Nominal capacity
Nominal producing water
Nominal power input
COP
Nominal current
Power supply
Nominal cycle water flow
WPD
Throttle type
Type
Refrigerant
Charging
Inlet
Pipes
Outlet
Air exhaust outlet
Fan power input (H/L)
Net weight
Gross weight
Operating weight
L
Unit dimensions
W
H
L
Packing
W
dimensions
H
Noise
Notes:
1.
The nominal heating capacity above is measured at outdoor environment DB/WB temperature
20ºC/15ºC, initial water tank temperature 15ºC, and final water temperature 55ºC;
2.
Nominal cycle water flow is the design value of unit heating cycle, WPD is measured at this
operation mode and water flow value;
3.
Noise level is measured at noise chamber whose background noise level is 11.5 dB(A), during
actual use, due to environmental noise or other reasons, the real noise may be different;
4.
All specifications are subjected to change by the manufacturer without prior notice.
Model
kW
l/h
kW
W/W
A
m³/h
kPa
kg
inch
inch
W
kg
kg
kg
mm
mm
mm
mm
mm
mm
dB(A)
UHA075B5
UHA100B5
30
40
645
860
6.83
8.71
4.39
4.59
13.2
17.3
380V/3N/50Hz
5.16
6.88
35
58
EXV
R410A
4.1
Rc1-1/2
Rc1-1/2
Rc1-1/2
Rc1-1/2
On top
490/180
680/190
220
250
248
278
225
255
990
990
840
840
1515
1515
1080
1080
890
890
1700
1700
60
62
UHA200B5
80
1720
18.22
4.39
33.4
13.76
72
5
5.0Х2
Rc2
Rc2
680Х2/190Х2
500
540
510
1990
840
1780
2070
890
1960
65
5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Uha100b5Uha200b5