Mounting & cable entry points
These instructions cover installation of the panel and battery box. The cards and
batteries are installed during the commissioning of the system by the servicing
organisation.
The control panel can be surface or fl ush mounted. The only time it should not be fl ush
mounted is when the battery box is close fi tted beneath the control panel.
Any unused knockouts that have been removed must not be left open.
Backplane
Dust
cover
over
backplane
0V
to printer
Floor level
a. Identify the package VIG1-24 / VIG1-72 and check that it contains all the parts.
b. Remove the temporary cover from the Back box.
c. Knock out/in the required cable entry points from the Control panel back box and
from the Battery box.
d. Use the fi xing points provided to mount the Back box and Battery box to the wall
using suitable fi xings.
www.acornfiresecurity.com
Cable entry points
Earth to
18 - Back
Inner door
21 - Top
3 - Bottom side (on the right)
Fitted on VIG1-72 only
www.acornfiresecurity.com
390mm
Vigilon fire system
8-off Earth points
(1-0ff bottom side
on the right hand)
Mains supply
cable
Knock outs
Adhesive backed foam pad
to seal up gap to prevent
ingress
PSU
Back box
for VIG-72 shown
5-off Backbox
fixing points
(includes
1 keyhole)
21