Auxiliary Relay Circuits - Honeywell Gent Vigilon Installation Instructions Manual

Panel based fire detection and alarm system
Table of Contents

Advertisement

Auxiliary relay circuits

Auxiliary relay circuits
The control panel operates the auxiliary contacts when the confi gured event is received
from the system.
The auxiliary relays 1 and 2 contacts can be used to control external equipment, such
as an automatic dialer that makes the call for fi re fi ghting action. The relays can be
individually re-confi gured to operate with either fi re, fault or disablement event in the
system.
The relay operation can also be delayed by up to 10 minutes and can be set up
to operate in a normally energised or de-energised state. The contacts should be
powered from an independent power supply, where required.
Change over contacts rated 1A @ 24Vdc,
to control external equipment
NC C NO NC C NO
P7
AUXILIARY
RELAY 1
Factory default:
Aux relay 1 is normally de-energised and operates with a
fire event without delay.
Aux relay 2 is normally energised and de-energises with a
fault event without delay.
Note: Aux relay 2 has been shown in the above diagram in
its de-energised state, which is the state when there is
no power to the panel.
30
www.acornfiresecurity.com
NC C NO NC C NO
Terminal Card
www.acornfiresecurity.com
P8
AUXILIARY
RELAY 2
PANEL
Configurable delayed
operation.
Up to 10 minutes delay