Additional Information For Profibus Dp; Additional Information For Connecting To Hart-Protocol - ABB MAG-SM Instruction Bulletin

Field mount housing and 19“-design
Table of Contents

Advertisement

9.1

Additional Information for Profibus DP

GSD File (Instrument Data Base File)
The name of the GSD file is FP6666.GSD and is included with the shipment.
Parameter Entry
Submenu
.Data link
9.2
Additional Information for Connecting to
®
HART-Protocol
The converter Instrument Tag includes the term HART-Protocol. The appropriate software can be recognized by the
label attached to the EPROM with the identification, e.g. D699B164U01 X.30, abbreviated as B164U01 X.30.
There are a number of parameter functions pre-installed in this software. The current output is set to 4-20 mA, the min. load
is 250 Ohm. Not all standard settings are available in HART. Please observe the note in Section 5.5.3
HART-Protocol, Data Entry, see Pages 19 to 26
Parameter Entry
Submenu
.Data link
Communication
ENTER
ASCII-Profib.DP
Slave-Addr.
126
Function
Param.-Profib.DP
.
Instr. Address
0
ENTER
Electromagnetic Flowmeter Converter
The communication mode Profibus DP is selected in the
Submenu Data Link.
The Slave-Address must always have 3 digits, Address-Range
000, 001 to 126. If a one or two digit bus address is entered, an
incorrect interpretation of the bus address will be made by the
converter.
This function can be used to access the parameters in the
Profibus DP-Module. See also Section 13 „Data Link Functions"
Part No.D184B093U02.
The instrument address can be set between 0 and 15.
If the Address is set to 0, then the current output value for the
flowrate is changed to the range from 4.00 to 20.00 mA. If
additional instruments are connected to the bus and an Address
1-15 is set, then the converter operates in the Multidrop-Mode.
The current output is then set to a fixed 4.00 mA value. The
evaluation of the measurement values is only possible using the
HART-Communication.