BACnet Configurations
• This will open 'BACnet Settings' and will list the BACnet MAC address, Baud rate, BACnet Config, Max
Master Address, and Device Instance
• Each item can be selected by touching the item on the screen. Once selected, changes can be made
The BACnet Facilitator will have the BACnet MAC Address. This does not come from us. If the caller is an end user,
he/she will need to contact a BACnet Facilitator.
The Baud Rate should only in very rare circumstances be adjusted. Rheem support does NOT under any
circumstances provide advice for this setting.
The BACnet config should always be left as MS/TP MASTER.
The Max Master Addr should always be left at 127 unless the BACnet Facilitator wants to change it. An end user
should never change this and Rheem support should never suggest it.
The device instance will also come from the BACnet facilitator. If the DI is 4194303, it is defaulting and not connected
to the network. The BACnet Facilitator will have to enter these numbers.
NOTE: Premium Triton units come with the wiring connector needed to connect unit to BACnet network.
THIS IS ONLY INCLUDED WITH PREMIUM MODELS.
NOTE: WE SHOULD ONLY ADVISE CALLERS WHERE TO GO TO ENTER/ADJUST THESE SETTINGS, AND
NEVER ATTEMPT TO PROVIDE THEM WITH THE CONFIGURATIONS.
Triton Service Manual SVC1020T ; Rev 4