8 8 | Bosch Climate 5000 Series Ductless Air Conditioner / Heat Pump Multi Zone Outdoor Units
9.4 Outdoor Unit - BMS500-AAM048-1CSXRA,
BMS500-AAM036-1CSXHB
9.4.1 Removing the fan assembly
1. Stop operation of the system and turn "OFF" the power at the disconnect.
2. Remove the air outlet grille (8 screws).
Figure 147
3. Remove the nut xing the fan, and remove the fan.
Figure 148
4. Remove the top cover (4 screws).
Data subject to change
Screws of top cover
Figure 149
5. Remove the front side panel (1 screw).
Figure 150
6. Disconnect the fan motor connectors FAN1 (3p, white) and FAN2 (3p, white)
from DC motor driver board.
Figure 151