Bosch Climate 5000 Series Service Manual page 81

Ductless air conditioner / heat pump multi zone outdoor units
Hide thumbs Also See for Climate 5000 Series:
Table of Contents

Advertisement

Service Manual
9.2.4 Removing the compressor
1. Follow steps outlined in Section 9.2.1.
2. Recover refrigerant from the refrigerant circuit.
3. Remove the sound insulation material and crankcase heating cable.
4. Remove terminal cover of compressor and disconnect wires of compressor
thermo and compressor from the terminal.
5. Apply heat and remove discharge and suction pipes.
Figure 121
6. Remove the hex nuts and washers xing the compressor on bottom plate.
Figure 122
7. Lift the compressor from the base pan assembly.
Bosch Thermotechnology Corp. | 08.2020
Bosch Climate 5000 Series Ductless Air Conditioner / Heat Pump Multi Zone Outdoor Units | 81
9.2.5 Removing the reactor
1. Follow steps outlined in Section 9.2.1.
2. Disconnect the connection between the reactor and IPM board.
3. Remove the cover of inductance (2 screws).
Figure 123
4. Disconnect two pieces of wires connected from the cover of inductance.
5. Remove the reactor (4 screws).
Figure 124
Inductance
Cover
Screws
Screws of
reactor
Data subject to change