9 Disassembly Guide

Pictures are provided as a reference only. Each unit will be different
depending on the your model number.

9.1 Outdoor Unit - BMS500-AAM018-1CSXRA

9.1.1 Removing the fan assembly
1. Stop operation of the system and turn "OFF" the power at the disconnect.
2. Remove the air outlet grille.
Figure 79
3. Remove the hex nut that is xing the fan.
Figure 80
4. Remove the fan.
Bosch Thermotechnology Corp. | 08.2020
Bosch Climate 5000 Series Ductless Air Conditioner / Heat Pump Multi Zone Outdoor Units | 71
5. Remove the top cover (3 screws).
Figure 81
6. Remove the black cover of the electrical control box.
Figure 82
7. Disconnect the fan motor connector CN14 (white, 3p) from IPM.
Figure 83
Screws