Installation Process; Outdoor Units Information - LG ARUN BTE4 Series Installation Manual

Table of Contents

Advertisement

Available languages

Available languages

4

INSTALLATION PROCESS

Indicate clearly who will be responsible for switch setting.
Determination of division work
Make connection clearly between outdoor, indoor,
Preparation of contract drawings
remote controller and option.
Take account of gradient
Sleeve and insert work
of drain piping
Check model name to
Installation of indoor unit
make sure the fitting
is made correctly
Special attention to dryness,
Refrigerant piping work
cleanness and tightness
Drain pipe work
Adjust to downward gradient
Make sure airflow is sufficient
Duct work
Make sure no gaps are left where
Heat insulation work
the insulating materials are joined
Multiple core cable must not be used.
Electrical work
(connection circuits and drive circuits)
(suitable cable should be selected)
In the final check for 24hours at 3.8 MPa(38.7 kgf/cm
Airtight test
must be no drop in pressure.
The vacuum pump used must have a capacity of reaching at least
Vacuum drying
5 torr, more than 1 hour
Recharge correctly as calculated in this manual. and record the
Additional charge of refrigerant
amount of added refrigerant
Make sure there are no gaps left between the facing materials
Fit facing panels
used on the ceiling
Refer to automatic addressing flowchart
Automatic addressing of indoor unit
Preheat the crank case with the electrical heater for more than 6 hours.
Run each indoor unit in turn to make sure the pipe work
Test run adjustment
has been fitted correctly
Explain the use of the system as clearly as possible to your customer and
Transfer to customer with explanation
make sure all relevant documentation is in order
CAUTION
!
• The above list indicates the order in which the individual work
operations are normally carried out but this order may be varied
where local conditions warrants such change.
• The thickness of the piping should comply with the relevant
local and national regulations for the designed pressure 3.8MPa.
• Since R410A is a mixed refrigerant, the required additional
refrigerant must be charged in its liquid state.(If the refrigerant
is charged in its gaseous state, its composition changes and the
system will not work properly.)

OUTDOOR UNITS INFORMATION

CAUTION
!
Combination Ratio(50~200%)
Outdoor Number
Single outdoor units
Double outdoor units
Triple outdoor units
Notes : * We can guarantee the operation only within 130%
Combination. If you want to connect more than 130%
combination, please contact us and discuss the
requirement like below.
• If the operation of indoor unit is more than 130%, the airflow is
operated as low in the all indoor units.
• The number of (
) means the number of Max. connectable
indoor units, when the connected capacity of indoor units is in
the table above.
Outdoor unit foundation work
The foundation must be level even
Installation of outdoor unit
Avoid short circuits and ensure
sufficient space is allowed for service
2
) there
Connection Ratio
200%
160%
130%
Power Supply : 220-240 V3~ 50Hz / 220 V3~ 60Hz
Model Name : ARUN***BTE4
Number of outdoor units
Capacity (HP)
8
Combination Unit
ARUN080BTE4
Model
Independent Unit
ARUN080BTE4
Dimensions
mm
(920×1,680×760)×1
Net Weight
kg
202 × 1
Refrigerant
7.5
kg
Precharged amount
9.52 (3/8)
Liquid mm (inch)
Pipe
Connctions
19.05 (3/4)
Gas
mm (inch)
13(20)
Number of maxmum connectable indoor units
Number of outdoor units
Capacity (HP)
14
Combination Unit
ARUN140BTE4 ARUN160BTE4 ARUN180BTE4 ARUN200BTE4
Model
Independent Unit
ARUN140BTE4 ARUN160BTE4 ARUN180BTE4 ARUN200BTE4
Dimensions
mm
(1,240×1,680×760)×1 (1,240×1,680×760)×1 (1,240×1,680×760)×1 (1,240×1,680×760)×1
Net Weight
kg
245 × 1
Refrigerant
kg
10.5
Precharged amount
Liquid mm (inch)
12.7 (1/2)
Pipe
Connctions
Gas
mm (inch)
28.58 (1 1/8)
Number of maxmum connectable indoor units
23(35)
Number of outdoor units
Capacity (HP)
22
Combination Unit
ARUN220BTE4 ARUN240BTE4 ARUN260BTE4 ARUN280BTE4
Model
ARUN120BTE4 ARUN120BTE4 ARUN140BTE4 ARUN160BTE4
Independent Unit
ARUN100BTE4 ARUN120BTE4 ARUN120BTE4 ARUN120BTE4
(920×1,680×760)×2 (920×1,680×760)×2 (1,240×1,680×760)×1 (1,240×1,680×760)×1
Dimensions
mm
Net Weight
kg
208 × 2
Refrigerant
7.5 × 2
kg
Precharged amount
15.88 (5/8)
Liquid mm (inch)
Pipe
Connctions
28.58 (1 1/8)
Gas
mm (inch)
35(44)
Number of maxmum connectable indoor units
Number of outdoor units
Capacity (HP)
30
Combination Unit
ARUN300BTE4 ARUN320BTE4 ARUN340BTE4 ARUN360BTE4
Model
ARUN180BTE4 ARUN200BTE4 ARUN200BTE4 ARUN200BTE4
Independent Unit
ARUN120BTE4 ARUN120BTE4 ARUN140BTE4 ARUN160BTE4
(1,240×1,680×760)×1 (1,240×1,680×760)×1 (1,240×1,680×760)×2 (1,240×1,680×760)×2
Dimensions
mm
+ (920×1,680×760)×1 + (920×1,680×760)×1
Net Weight
kg
280 × 1 + 208 × 1 280 × 1 + 208 × 1 280 × 1 + 245 × 1 280 × 1 + 245 × 1
Refrigerant
kg
10.5 + 7.5
Precharged amount
Liquid mm (inch)
19.05 (3/4)
Pipe
Connctions
Gas
mm (inch)
34.9 (1 3/8)
49(60)
Number of maxmum connectable indoor units
Number of outdoor units
2 Outdoor Unit
Capacity (HP)
38
Combination Unit
ARUN380BTE4 ARUN400BTE4 ARUN420BTE4 ARUN440BTE4
ARUN200BTE4 ARUN200BTE4 ARUN180BTE4 ARUN200BTE4
Model
Independent Unit
ARUN180BTE4 ARUN200BTE4 ARUN140BTE4 ARUN140BTE4
(1,240×1,680×760)×2 (1,240×1,680×760)×2 (1,240×1,680×760)×2 (1,240×1,680×760)×2
Dimensions
mm
280 × 2
Net Weight
kg
10.5 × 2
Refrigerant
kg
Precharged amount
Liquid mm (inch)
19.05 (3/4)
Pipe
Connctions
Gas
mm (inch)
41.3 (1 5/8)
Number of maxmum connectable indoor units
61(64)
1 Outdoor Unit
10
12
ARUN100BTE4
ARUN120BTE4
ARUN100BTE4
ARUN120BTE4
(920×1,680×760)×1
(920×1,680×760)×1
208 × 1
208 × 1
7.5
7.5
9.52 (3/8)
12.7 (1/2)
22.2 (7/8)
28.58 (1 1/8)
16(25)
20(30)
1 Outdoor Unit
16
18
20
245 × 1
280 × 1
280 × 1
10.5
10.5
10.5
12.7 (1/2)
15.88 (5/8)
15.88 (5/8)
28.58 (1 1/8)
28.58 (1 1/8)
28.58 (1 1/8)
26(40)
29(45)
32(50)
2 Outdoor Unit
24
26
28
+ (920×1,680×760)×1 + (920×1,680×760)×1
208 × 2
245 × 1 + 208 × 1 245 × 1 + 208 × 1
7.5 × 2
10.5 + 7.5
10.5 + 7.5
15.88 (5/8)
19.05 (3/4)
19.05 (3/4)
34.9 (1 3/8)
34.9 (1 3/8)
34.9 (1 3/8)
39(48)
42(52)
45(56)
2 Outdoor Unit
32
34
36
10.5 + 7.5
10.5 × 2
10.5 × 2
19.05 (3/4)
19.05 (3/4)
19.05 (3/4)
34.9 (1 3/8)
34.9 (1 3/8)
41.3 (1 5/8)
52(64)
55(64)
58(64)
3 Outdoor Unit
40
42
44
ARUN100BTE4 ARUN100BTE4
+ (920×1,680×760)×1 + (920×1,680×760)×1
280 × 2
280 × 1 + 245 × 1
280 × 1 + 245 × 1
+ 208 × 1
+ 208 × 1
10.5 × 2
(10.5 × 2) + 7.5 (10.5 × 2) + 7.5
19.05 (3/4)
19.05 (3/4)
19.05 (3/4)
41.3 (1 5/8)
41.3 (1 5/8)
41.3 (1 5/8)
64
64
64