Cable Adjustment
A.
Check that the circuit breaker turns OFF and ON by
moving the operating handle up for ON and down for OFF
If the breaker does not switch ON, loosen the cable
mounting nuts at the fixed plate tab. Hold the operating
handle in the maximum ON position and move the cable
toward the top of the breaker. Retighten the mounting
nuts to secure.
B.
Trip the circuit breaker by pushing the PUSH TO TRIP
button
C. Check that the circuit breaker resets by moving the
operating handle from ON to OFF and back to ON. If the
breaker resets, tighten the spring adjuster one additional
turn. Attach lockwashers and 1/4-28 nut to the end of the
cable rod and tighten to 32 in. Ib.
D.
If the circuit breaker does not reset, tighten the spring
adjusters one turn and repeat Steps B and C. Continue
this procedure until the breaker resets then tighten the
adjusters one additional turn and secure with lockwashers
and nut.