Siemens I-T-E Sensitrip MD Series Information And Instruction Manual page 11

Molded case circuit breakers
Table of Contents

Advertisement

MD and ND-Frame Trip Adjustments
Figure 1
I
= Maximum circuit breaker ampere rating.
n
I
= Current Rating—a function of continuous ampere adjust-
r
ment setting expressed in % of I
Adjustable Instantaneous Trip Switch
x I
r
Instantaneous settings are multiples of the continuous cur-
rent setting.
NOTE: Maximum instantaneous trip is 10,000 Amps—with
instantaneous setting on "MAX", time delay is eliminated.
n
I
= Ground Fault Pickup—a function of adjustment setting
g
expressed in % of I
.
n
Adjustable Ground Fault Pickup
Pickup I
=%I
g
n
2
Delay 1
t @ 51n
Ground fault protection is available for 3 phase, 3 wire and 3
phase 4 wire (neutral) electrical systems. SMD/SND models
with an adjustable ground fault delay switch allow for the
selection of ground fault pickup at 20, 25, 30, 40, 55 or 70%
of the maximum amps rating (%I
or .4 sec @ .5 x I
See Figure 1 for possible settings for this
n
switch
2
), with an 1
t delay of .1, .2,
n
9

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

I-t-e sensitrip nd seriesI-t-e sensitrip smd69600aI-t-e sensitrip smd69700aI-t-e sensitrip smd69800aI-t-e sensitrip smd69600agI-t-e sensitrip smd69700ag ... Show all

Table of Contents