THE MICROCOMPUTER CONTROL CENTER

PROGRAMMING SYSTEM SETPOINTS

The system setpoints can be entered at any time . . . . .
even when the system is running. Proceed as follows to
enter system setpoints. (Refer to Fig. 5.)
1. Press ACCESS CODE key.
2.
ENTER VALID ACCESS CODE _ _ _ _
3. Using ENTRY keys, enter 9 6 7 5.
4. As each digit is entered, the characters Y O R K are
displayed.
NOTE: If digits other than 9 6 7 5 are entered,
Y O R K is still displayed.
NOTE: For ease in remembering the code, note that
the letters Y O R K correspond to the dig-
its 9 6 7 5 on a telephone dial .
5. Press ENTER key.
NOTE: If digits other than 9 6 7 5 were entered in step
No. 4,
INVALID ACCESS CODE
when the ENTER key is pressed. If this oc-
curs, enter the correct access code (9675)
and proceed.
6.
ACCESS TO PROGRAM KEY AUTHORIZED
NOTE: Unless terminated by pressing the ACCESS
CODE key again, the operator will have ac-
cess to the PROGRAM key for 10 minutes.
When 10 minutes have elapsed, access to
PROGRAM key will be automatically disabled
and the operator must return to step No. 1 to
gain access.
7. Press PROGRAM key.
8.
PROGRAM MODE, SELECT SETPOINT
14
PROGRAMMING
is displayed.
FIG. 5 – KEYPAD – PROGRAMMING SYSTEM
9. Enter setpoints as detailed below. If you make a mis-
is displayed
take when entering a value, press CANCEL key and
then ENTER key. The display will revert to the default
values and the cursor will return to the first change-
able digit. You can then proceed to enter the correct
values. If the entered value exceeds acceptable lim-
is displayed.
its,
message will be displayed for 2 seconds, then the
PROGRAM MODE, SELECT SETPOINT
appear.
10. When all the desired setpoints have been entered,
press the ACCESS CODE key to exit PROGRAM
mode and terminate access to PROGRAM mode.
ACCESS TO PROGRAM MODE DISABLED
The Control Center will automatically return to LO-
CAL, REMOTE or SERVICE mode . . . . whichever
is displayed.
was last selected.
SETPOINTS
OUT OF RANGE – TRY AGAIN!
LD00954
message will re-
is displayed.