Troubleshooting; Causes Of Normal And Safety System Shutdowns - York Millennium YK M3 M3 G4 THRU YK S6 S4 J2, YK LB LB G4 THRU YK SE SC J4 Operating & Maintenance Manual

Centrifugal liquid chillers with microcomputer control center
Table of Contents

Advertisement

TABLE 1 – CAUSES OF NORMAL AND SAFETY SYSTEM SHUTDOWNS IN ACCORDANCE WITH THE MICROCOMPUTER CONTROL,
CENTER DISPLAY
SHUTDOWN CAUSE
CONTROL CENTER DISPLAY
DAY OF
TIME OF
CAUSE OF
WEEK
DAY
SHUTDOWN
MON.
10:00 AM
Low Water
Temp.
MON.
10:00 AM
Flow Switch
MON.
10:00 AM
System
Cycling
MON.
10:00 AM
Multi-Unit
MON.
10:00 AM
Internal
Clock
MON.
10:00 AM
AC under-
voltage
MON.
10:00 AM
Power Fault
Remote Stop
MON.
Anti-Recycle,
20 Min. Left
GOVERNING CONTROL FUNCTION
METHOD OF
DESCRIPTION
RESTART
ON
RISE
Autostart
Low Water
Chilled
(LWT)
water
setpoint
Autostart
Flow Switch
Autostart
A remote com-
mand (computer
relay contact or
manual switch)
Autostart
(Optional) Lead-
Lag Sequence
Control
Autostart
Internal Clock
Autostart
<15% FLA for
25 continuous
seconds
Autostart
CM-2 Current
Module or
Solid State
Starter
Energy manage-
ment System
Anti-Recycle
timer
PROGRAMMED
OPERATING
SETPOINTS
POINT
BY OPERATOR
ON
FALL
4°F below
4°F below chilled
chiller
water setpoint
water
(If set to 40°F
setpoint
would be 36°F)
(36°F minimum
Daily Schedule
Programmed to
Shutdown Unit
Will not start
until 30 Min.
timer is timed
START-UP OF
PROBABLE CAUSE
SYSTEM AFTER
AND SERVICE
SHUTDOWN
REQUIRED
Automatic Restart
System load is less
when water reaches
than minimum
setpoint; if system
capacity
is running and set-
point is increased
4°F, system will
continue to run, as
LWT cutout shifts
to a fixed 36°F for
10 minutes.
Automatic Restart
Lack of water flow.
when water flow is
Check operation of
Restored to close
chilled water pump
flow switch.
Automatic Restart
Contact-connected to
upon remote
the Remote/Local
command.
cycling input of the
Digital input board
Automatic Restart
Contact-connected to
upon remote
the Multi-Unit cycling
command.
input of the Digital
input board
Will automatically
Pressing Compressor
restart when pro-
Start Switch over-
grammed schedule
rides the program
permits
Cycling shutdown oc-
curs when motor cur-
rent is >15% FLA for
25 seconds during
chiller operation
Will start automatic-
Motor Controller con-
tically following
tacts opening and
coastdown
closing in less than 3
seconds due to a power
fault condition
Start up by start
Remote Stop Contact
signal from remote
Closure
start switch
Will restart when
Min. Time between
time left = 00 Min.
successive compres-
sor starts is 30 min.