Static Resistances; Electric Heater Cfm Limitations - York SUNLINE 2000 DM 048 Technical Manual

Single package gas/electric units and single package air conditioners
Table of Contents

Advertisement

036-21502-003-A-1105
TABLE 15: STATIC RESISTANCES
DESCRIPTION
1 3
ECONOMIZER
ELECTRIC
7-15KW
1
HEATERS
20-30KW
BOTTOM DUCT CONNECTIONS
2
COOLING ONLY
1. Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.
2. Add these resistance values to the available static resistance values on SUPPLY AIR BLOWER PERFORMANCE Tables.
3. The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air
duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
TABLE 16: ELECTRIC HEATER CFM LIMITATIONS
UNITMODEL SIZE NOMINAL
TONS
3
4
5
6
Unitary Products Group
1000
1200
1400
0.07
0.08
0.09
0.04
0.05
0.06
0.06
0.07
0.08
1
0.06
0.07
0.08
0.08
0.10
0.12
VOLTAGE
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
RESISTANCE, IWG
CFM
1600
1800
2000
0.11
0.13
0.15
0.07
0.08
0.10
0.09
0.11
0.13
0.09
0.10
0.11
0.14
0.16
0.18
MINIMUM SUPPLY AIR CFM
HEATER SIZE NOMINAL KW
5
7
10
1100
1100
1200
1100
1100
1200
-
1100
1200
-
-
1200
1300
1300
1300
1300
1300
1300
-
1300
1300
-
-
1300
1600
1600
1600
1600
1600
1600
-
1600
1600
-
1600
1600
1800
1800
1800
-
1800
1800
-
-
1800
2200
2400
2600
2800
0.17
0.20
0.23
0.26
0.12
0.14
0.16
0.19
0.15
0.17
0.20
0.23
0.12
0.14
0.16
0.19
0.20
0.23
0.26
0.29
15
20
1200
1300
1200
1300
1200
1300
1200
1300
1300
1300
1300
1300
1300
1300
1300
1400
1600
1600
1600
1600
1600
1600
1600
1600
1800
1800
1800
1800
1800
1800
3000
0.30
0.22
0.26
0.22
0.32
30
-
-
-
-
-
-
-
-
1600
1600
1600
1800
1800
1800
1800
25