530.26-TG3YI
UNIT DIMENSIONS - D*CG180 & 240 UNITS
3181 (125-1/4") (180)
3561 (136-1/4") (240)
CLEARANCES (mm / in. )
1
Front
914 / 36
610 / 24 (Less Economizer)
Back
1245 / 49 (With Economizer)
610 / 24 (Less Economizer)
Left Side (Filter Access)
1372 / 54 (With Economizer)
Right Side (Outdoor Coil) 914 / 36
2
Below Unit
0 / 0
1829 / 72 with 914 / 36 maximum
3
Above Unit
Horizontal Overhang
1
Locate unit so that the vent air outlet hoods are at least:
0.9 meter (3 ft) above any forced air inlet located within 3.0m (10 ft) horizontal
(excluding those integral to the unit).
1.2 meters (4 ft) below, 1.2m (4 ft.) horizontal from, or 0.31m(1 ft) above any door
or gravity air inlet into the building.
1.2 meters (4 ft) from electric meters, gas meters, regulators and relief equipment.
2
Units may be installed on combustible surfaces capable of continuous exposure to
temperatures of 92 C (197 F), and intermittent exposure to temperatures of 124 C (255 F).
3
Units must be installed outdoors. Overhanging structures or shrubs should not
obstruct the outdoor air discharge outlet.
NOTE: A 25mm (1 in.) clearance must be provided between any combustible material and the
supply air ductwork for a distance of 0.9m (3 ft) from the unit.
The products of combustion must not be allowed to accumulate within a confined space
and recirculate.
16
616 (24-1/4") (180)
895 (35-1/4") (240)
(For Outdoor Air Discharge)
1235 (48-5/8") (180)
1337 (52-5/8") (240)
All dimensions are in millimeters and inches,
unless otherwise specified. They are subject to
change without notice. Certified dimensions
will be provided upon request.
UTILITIES ENTRY DATA
OPENING
HOLE
DIAMETER*
(in. / mm)
1-1/8 / 29 KO
A
3/4 NPS / 19 (Fem.)
3-5/8 / 92 KO
B
3 NPS / 76 (Fem.)
C
2-3/8 / 60 KO
D
1-11/16 / 43 Hole
*
KO denotes Knockout facility.
**
Opening in the bottom of the unit can be located by the slice in the insulation.
RETURN AIR
SUPPLY AIR
OUTDOOR AIR
(Discharge)
OUTDOOR AIR
(Economizer)
USED FOR
Front
Control Wiring
Bottom
Front
Power Wiring
Bottom
Gas Piping (Front)
Gas Piping (Bottom)**
Unitary Products Group