Unit Dimensions; Unit Clearances - York PREDATOR 120 Installation Manual

Single package air conditioners and single package electric units
Hide thumbs Also See for PREDATOR 120:
Table of Contents

Advertisement

035-17311-002-A-0803
Do not permit overhanging structures or shrubs to
obstruct condenser air discharge outlet, combustion
air inlet or vent outlets.
FIGURE 8 -

UNIT DIMENSIONS

TABLE 6: UNIT CLEARANCES
*
72"
Top
Front
36"
36"
Rear
*.
Units must be installed outdoors. Overhanging struc-
ture or shrubs should not obstruct condenser air dis-
charge outlet.
†.
To remove the slide-out drain pan, a rear clearance of
sixty inches is required. If space is unavailable, the
drain pan can be removed through the front by separat-
ing the corner wall.
‡.
Units may be installed on combustible floors made from
wood or class A, B or C roof covering materials.
DETAIL A
Unitary Products Group
Right
12"
Left
36"
0"
Bottom
NOTE: A one-inch clearance must be provided between
any combustible material and the supply ductwork
for a distance of 3 feet from the unit.
DETAIL B
DETAIL C
13