Unit Dimensions (Rear View); Disconnect/Blower Access Location; Utilities Entry; Minimum Clearances - York DM 036 Technical Manual

Single package gas/electric units and single package air conditioners
Hide thumbs Also See for DM 036:
Table of Contents

Advertisement

FIGURE 7:

UNIT DIMENSIONS (REAR VIEW)

FIGURE 8:
DISCONNECT/BLOWER ACCESS
LOCATION
TABLE 27: UTILITIES ENTRY
HOLE
OPENING SIZE (DIA.)
A
1
7/8" KO
2" KO 1
B
C
1-5/8" KO
D
1-1/2" KO
1. Opening in the bottom to the unit can be located by the
side in the insulation.
2. Do not remove the 2" knockout ring.
34
USED FOR
Side
2
Control Wiring
Bottom
Side
Power Wiring
Bottom
Gas Piping (Front)
Gas Piping (Bottom)
TABLE 28: MINIMUM CLEARANCES
LOCATION
Front
Back
Left Side (Filter Access)
Right Side (Cond. Coil)
1
Below Unit
2
Above Unit
1. Units may be installed on combustible floors made
from wood or class A, B, or C roof covering material.
2. Units must be installed outdoors. Overhanging struc-
tures or shrubs should not obstruct condenser air dis-
charge outlet.
036-21502-002-A-0303
CLEARANCE
24" (Cooling/Electric Heat)
32" (Gas Heat)
12" (Less Economizer)
36" (With Economizer or Fixed
Air/Motorized Damper)
24" (Less Economizer)
36" (With Economizer)
24"
0"
72" (For
Condenser Air Discharge)