Unit Dimensions (Rear View); Disconnect/Blower Access Location; Utilities Entry; Minimum Clearances - York Sunline 2000 Technical Manual

Single package gas/electric units and single package
Hide thumbs Also See for Sunline 2000:
Table of Contents

Advertisement

mm[inch]
445
[17
1
/
]
2
FIGURE 7 -

UNIT DIMENSIONS (REAR VIEW)

Filter Access
Blower Motor Access
Dot Plugs
Field-Supplied Disconnect
Switch Location
Mounting Bracket for
Disconnect Switch
(Field Supplied)
Disconne t Switch Location
and Motor Access Panel for
Unit with "Belt-Drive" Option
FIGURE 8 -
DISCONNECT/BLOWER ACCESS
LOCATION
TABLE 18: UTILITIES ENTRY
OPENING SIZE (DIA.)
HOLE
(mm/in)
A
1
22 / 0.88 KO
51 / 2.0 KO 1
B
C
41 / 1.63 KO
D
38 / 1.5 KO
1. Opening in the bottom to the unit can be located by the
side in the insulation.
2. Do not remove the 2" knockout ring.
Johnson Controls Unitary Products
165
445
[6
1
/
]
[17
1
/
]
2
2
200
[7
A,B
Wiring Entry
Control Box Access
(See Detail "B")
USED FOR
Side
2
Control Wiring
Bottom
Side
Power Wiring
Bottom
Gas Piping (Front)
Gas Piping (Bottom)
292
[11
1
/
]
2
76 [3]
292
[11
1
/
]
2
5
117 [4
/
]
8
7
/
]
8
TABLE 19: MINIMUM CLEARANCES
LOCATION
Front
Rear
Left Side (Filter Access)
Right Side (Cond. Coil)
Below Unit
Above Unit
1. Units may be installed on combustible floors made from
wood or class A, B, or C roof covering material.
2. Units must be installed outdoors. Overhanging struc-
tures or shrubs should not obstruct condenser air dis-
charge outlet.
637367-XTG-B-1110
CLEARANCE (mm / In.)
610 / 24.0 (Cooling/Electric Heat)
813 / 32.0 (Gas Heat)
305 / 12.0 (Less Economizer)
914 / 36.0 (With Economizer or
Fixed Air/Motorized Damper)
610 / 24.0 (Less Economizer)
914 / 36.0 (With Economizer)
610 / 24.0
1
0
1829 / 72.0 (For
2
Condenser Air Discharge)
23