Dh036 Cooling Capacities (3 Ton) - York DH 036 Technical Manual

Single package gas/electric units and single package air conditioners
Hide thumbs Also See for DH 036:
Table of Contents

Advertisement

TABLE 4: DH036 COOLING CAPACITIES (3 TON)
AIR ON
EVAPORATOR
TOTAL
COIL
1
CAP.
INPUT
MBH
CFM
WB °F
72
55.2
67
49.1
1500
62
44.7
57
42.4
72
55.2
67
49.1
1350
62
44.7
57
42.4
72
51.9
67
46.1
1200
62
42.0
57
39.8
72
49.4
67
43.9
1050
62
40.0
57
37.9
72
46.9
67
41.7
900
62
38.0
57
36.0
AIR ON
EVAPORATOR
TOTAL
COIL
1
CAP.
INPUT
MBH
CFM
WB °F
72
47.6
67
42.5
1500
62
38.0
57
37.4
72
46.5
67
41.6
1350
62
37.1
57
36.5
72
45.4
67
40.6
1200
62
36.2
57
35.7
72
43.2
67
38.7
1050
62
34.5
57
34.0
72
41.1
67
36.7
900
62
32.8
57
32.3
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower from the SUPPLY AIR BLOWER PERFORMANCE
Tables, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor
power input is 0.36kW. Refer to SUPPLY AIR BLOWER PERFORMANCE Tables for the kW of the supply air blower motor.
NOMINAL RATING
16
TEMPERATURE OF AIR ON CONDENSER COIL
85°F
SENSIBLE CAPACITY
POWER
ENTERING DRY BULB, °F
2
kW
86
83
80
77
3.18
35.2 30.7 26.2 21.8 17.3
3.13
41.7 37.2 32.8 28.3 23.8 19.4 14.9
3.05
44.7 43.6 39.1 34.6 30.1 25.7 21.2
3.05
42.4 42.4 42.4 37.9 33.4 29.0 24.5
3.18
35.2 30.7 26.2 21.8 17.3
3.13
41.7 37.2 32.8 28.3 23.8 19.4 14.9
3.05
44.7 43.6 39.1 34.6 30.1 25.7 21.2
3.05
42.4 42.4 42.4 37.9 33.4 29.0 24.5
3.15
30.0 26.5 23.0 19.5
3.10
35.7 32.2 28.7 25.2 21.7 18.2 14.7
3.02
41.2 37.7 34.2 30.7 27.2 23.7 20.2
3.03
39.8 39.8 37.3 33.8 30.3 26.8 23-3
3.12
27.3 24.3 21.2 18.2
3.07
32.6 29.6 26.5 23.5 20.5 17.4 14.4
2.99
37.7 34.7 31.6 28.6 25.6 22.5 19.5
3.00
37.9 37.0 34.5 31.4 28.4 25.4 22.3
3.09
24.6 22.1 19.5 16.9 14.4
3.04
29.5 26.9 24.4 21.8 19.2 16.7 14.1
2.96
34.2 31.6 29.1 26.5 23.9 21.4 18.8
2.97
36.0 34.2 31.7 29.1 26.5 24.0 21.4
TEMPERATURE OF AIR ON CONDENSER COIL
105°F
SENSIBLE CAPACITY
POWER
ENTERING DRY BULB, °F
2
kW
86
83
80
77
3.65
32.3 27.8 23.3 18.9 14.4
3.56
39.0 34.5 30.0 25.6 21.1 16.6 12.1
3.49
38.0 38.0 36.6 32.1 27.6 23.1 18.7
3.54
37.4 37.4 37.4 32.9 28.5 24.0 19.5
3.62
29.7 25.8 21.8 17.8 13.8
3.53
36.0 32.0 28.0 24.0 20.1 16.1 12.1
3.46
37.1 36.6 34.1 30.1 26.1 22.2 18.2
3.52
36.5 36.5 35.2 31.2 27.2 23.3 19.3
3.60
27.2 23.7 20.2 16.7 12.2
3.51
33.0 29.5 26.0 22.5 19.0 15.5 12.0
3.44
36.2 35.2 31.7 28.2 24.7 21.2 17.7
3.49
35.7 35.7 33.0 29.5 26.0 22.5 19.0
3.57
24.6 21.6 18.5
-
3.48
29.9 26.9 23.8 20.8 17.8 14.7 11.7
3.41
33.9 32.1 29.0 26.0 23.0 19.9 16.9
3.47
34.0 32.9 30.3 27.2 24.2 21.2 18.1
3.54
22.0 19.4 16.8 14.3 11.7
3.45
26.8 24.2 21.7 19.1 16.5 14.0 11.4
3.39
31.5 28.9 26.4 23.8 21.2 18.7 16.1
3.44
32.3 30.1 27.5 24.9 22.4 19.8 17.2
1
TOTAL
POWER
1
CAP.
INPUT
MBH
74
71
68
-
-
51.5
3.44
45.8
3.35
41.2
3.30
39.9
3.35
-
-
50.0
3.41
44.5
3.32
40.0
3.27
38.8
3.32
-
16.0
-
48.6
3.38
43.2
3.29
38.9
3.23
37.6
3.29
-
15.2
-
46.4
3.36
41.2
3.27
37.1
3.21
35.9
3.27
-
-
44.2
3.34
39.3
3.25
35.4
3.20
34.2
3.25
1
TOTAL
POWER
1
CAP.
INPUT
MBH
74
71
68
-
-
43.6
3.85
39.3
3.76
34.8
3.67
34.9
3.73
-
-
42.9
3.83
38.6
3.74
34.2
3.66
34.3
3.72
-
-
42.2
3.82
37.9
3.73
33.6
3.64
33.7
3.70
12.5
-
-
40.1
3.78
36.1
3.69
32.0
3.61
32.1
3.67
-
-
38.0
3.75
34.2
3.66
30.3
3.58
30.4
3.64
036-21506-003-C-0405
95°F
SENSIBLE CAPACITY
ENTERING DRY BULB, °F
2
kW
86
83
80
77
74
34.1 29.7 25.2 20.7 16.2
40.2 35.7 31.3 26.8 22.3 17.8 13.4
41.2 41.2 38.8 34.3 29.8 25.3 20.9
39.9 39.9 39.9 35.4 31.0 26.5 22.0
31.5 27.5 23.6 19.6 15.6
37.2 33.2 29.2 25.3 21.3 17.3 13.3
40.0 39.2 36.3 32.3 28.3 24.3 20.3
38.8 38.8 37.5 33.5 29.6 25.6 21.6
28.9 25.4 21.9 18.4 14.9
34.2 30.7 27.2 23.7 20.2 16.7 13.2
38.9 37.2 33.7 30.2 26.7 23.2 19.8
37.6 37.6 35.1 31.6 28.1 24.6 21.1
26.2 23.2 20.2 17.2 14.1
31.1 28.1 25.0 22.0 19.0 16.0 12.9
36.2 34.1 31.1 28.0 25.0 22.0 18.9
35.9 34.9 32.3 29.3 26.3 23.2 20.2
23.6 21.0 18.4 15.9 13.3
28.0 25.4 22.9 20.3 17.7 15.2 12.6
33.5 30.9 28.4 25.8 23.2 20.7 18.1
34.2 32.1 29.5 27.0 24.4 21.8 19.3
115°F
SENSIBLE CAPACITY
ENTERING DRY BULB, °F
2
kW
86
83
80
77
74
30.4 26.0 21.5 17.0 12.5
37.8 33.3 28.8 24.3 19.9 15.4 10.9
34.8 34.8 34.4 29.9 25.4 20.9 16.5
34.9 34.9 34.9 30.5 26.0 21.5 17.0
28.0 24.0 20.0 16.0 12.0
34.8 30.8 26.8 22.8 18.8 14.9 10.9
34.2 34.0 32.0 28.0 24.0 20.0 16.0
34.3 34.3 32.9 28.9 24.9 21.0 17.0
25.5 22.0 18.5 15.0 11.5
31.8 28.3 24.8 21.3 17.8 14.3 10.8
33.6 33.1 29.6 26.1 22.6 19.1 15.6
33.7 33.7 30.9 27.4 23.9 20.4 16.9
22.9 19.9 16.9 13.8 10.8
28.7 25.7 22.6 19.6 16.6 13.5 10.5
31.6 30.0 27.0 23.9 20.9 17.9 14.9
32.1 30.9 28.2 25.1 22.1 19.1 16.0
20.4 17.8 15.2 12.7 10.1
25.6 23.0 20.4 17.9 15.3 12.7 10.2
29.5 26.9 24.4 21.8 19.2 16.7 14.1
30.4 28.0 25.4 22.9 20.3 17.7 15.2
Unitary Products Group
1
71
68
-
-
-
-
-
-
-
-
-
-
1
71