Maximum Limitation In D.h.w. Heating Mode; Maximum Limitation Of The Secondary Return Temperature - Siemens RVD230 Basic Documentation

District heating and domestic hot water controller
Table of Contents

Advertisement

Example
Siemens Building Technologies
HVAC Products

27.2.3 Maximum limitation in d.h.w. heating mode

In contrast to maximum limitation in heating mode, maximum limitation of the primary
return temperature in d.h.w. mode uses a constant value. It is to be set on operating
line 176.
In order to reach the required anti-legionella temperature in the storage tank, a specific
maximum return temperature setpoint is used during the time the legionella function is
active. If that setpoint is set inactive (operating line 180 =
limitation of the return temperature during the time the legionella function is active.
For the mode of operation, refer to the table in subsection 27.2.1 "General" in this chap-
ter.
When both the heating and the d.h.w. circuit call for heat and maximum limitation of the
return temperature acts on both circuits, the higher of the 2 limit values applies.
If, with plant type 1–3, maximum limitation of the return temperature is deactivated
(entry ---), the d.h.w. temperature will be controlled according to the return temperature
acquired with sensor B72 because there is no sensor in the d.h.w. flow. The controlled
setpoint is the sum of the current d.h.w. setpoint plus the charging boost (operating line
116).
The current d.h.w. setpoint is generated internally and can be visualized as follows:
Select operating line 26 and press
27.3
Maximum limitation of the secondary return
temperature
The secondary return temperature of both the heating and the d.h.w. circuit can be
limited at a maximum, depending on the type of plant. The limit value is to be entered
on operating line 177 as a reduction to the current limit value of the maximum limitation
of the primary return temperature.
This function can become active only when the respective maximum limitation of the
primary return temperature (heating circuit or d.h.w.) is switched on. It can be deacti-
vated on operating line 171 for the heating circuit return, and on operating line 176 for
the d.h.w. return.
With plant type 3–7, the parameters are selected as follows:
Operating line 171 = 1
Operating line 172 = 70 °C
Operating line 173 = 7
Operating line 174 = 10 °C
Operating line 175 = 50 °C
Operating line 176 = 55 °C
Operating line 177 = 5 °C
When the outside temperature changes, the maximum limitations will change also:
Outside
temperature
Primary side
15 °C
50 °C (operating
line 175)
–5 °C*
60.5 °C**
–20 °C
70 °C (operating
line 172)
*
With shifting compensation
** Equation according to subsection "27.2.2 "Maximum limitation in heating mode "
Basic Documentation RVD230
27 Function block DRT and maximum limitation of the return temperature
.
Maximum limitation of the return temperature heating
circuit ON
Upper constant value
Slope
Start of compensation at an outside temperature of 10 °C
Lower constant value
Maximum limitation of the return temperature in the d.h.w.
circuit
Reduction on the secondary side
Heating circuit
Secondary side
45 °C (operating
line 175...177)
55.5 °C
65 °C (operating
line 172...177)
), there will be no maximum
- - -
D.h.w. circuit
Primary side
Secondary side
55 °C (operat-
50 °C (operating
ing line 176)
line 176...177)
CE1P2383en
97/130
27.05.2004