Function Block Display Of Actual Sensor Values; Operating Lines; Displays - Siemens RVD230 Basic Documentation

District heating and domestic hot water controller
Table of Contents

Advertisement

Siemens Building Technologies
HVAC Products
8
Function block Display of actual sen-
sor values
8.1

Operating lines

Line
Function, parameter
24
Room temperature (terminal A6)
25
Outside temperature
26
D.h.w. temperature
27
Flow temperature heating circuit
8.2

Displays

• Room temperature:
If a room temperature sensor or room unit is connected to the PPS interface (A6), the
temperature acquired will be displayed
• Outside temperature:
The displayed temperature is delivered by the analog outside sensor (connected to B9)
or via data bus (refer to subsection 21.2.4 "Outside temperature source").
If buttons
and
are pressed for 3 seconds, the displayed outside temperature will
be adopted as the composite and the attenuated outside temperature (outside tem-
perature reset)
• D.h.w. temperature:
The temperature displayed is that acquired with the d.h.w. sensor. Depending on the
plant configuration, this can be d.h.w. flow sensor B3 (plant types x–4) or storage tank
sensor B31 (other plant types with the exception of x–0).
If button
or
is pressed, the controller will display the current setpoint
• Flow temperature heating circuit:
The temperature displayed is that measured with sensor B1.
Exceptions:
Plant types 3–x and 7–2:
The temperature displayed is that measured with sensor B12
Plant types 0–x:
No display
If button
or
is pressed, the controller will display the current setpoint
Basic Documentation RVD230

8 Function block Display of actual sensor values

Unit
Factory setting
°C
Display function
°C
Display function
°C
Display function
°C
Display function
Range
33/130
CE1P2383en
27.05.2004