Siemens RVD230 Basic Documentation page 76

District heating and domestic hot water controller
Table of Contents

Advertisement

76/130
Siemens Building Technologies
HVAC Products
T
BWx
T
BWw
T
- SD
BWw
BW
T
- SD
- 2 K
BWw
BW
ON
1
OFF
ON
2
OFF
ON
3
OFF
4
Circulating pump
Forced charging
Release of the legionella function
Start conditions for the legionella function met
Start dwelling time
Reset dwelling time
Start dwelling time
Dwelling time has elapsed
T
D.h.w. temperature
BWx
T
D.h.w. temperature setpoint
BWw
SD
Switching differential of d.h.w. heating
BW
t
Time
If a maximum d.h.w. charging time has been set, it also acts here. If the legionella set-
point is not reached, the legionella function will be interrupted and resumed on comple-
tion of the maximum charging time.
The legionella setpoint will not be affected by the maximum of the d.h.w. temperature
setpoint.
Basic Documentation RVD230
18 Function block Extra legionella functions
5
6
7
8
t
CE1P2383en
27.05.2004

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents