FX0N-32NT-DP Profibus-DP Interface Unit
4.11.1

General Error (BFM #29 Bit 0)

When a general error occurs (bit 0 = ON) the 32NT-DP tries to send the data of BFM #28 and
#29 as a static diagnosis message to the DP-master. In this case data can not be exchanged
with the DP-master. After bit 0 returns to OFF, the static diagnosis message is also reset.
4.11.2

External 24V Power Error (BFM #29 Bit 2)

If a 24V DC power supply failure occurs, this bit is ON. If this error occurs, check 24V DC
power supply of the 32NT-DP.
4.11.3

Hardware Error (BFM #29 Bit 3)

If a hardware error of the 32NT-DP occurs, this bit is ON. If this error occurs, please contact a
service representative.
4.11.4

EEPROM Error (BFM #29 Bit 4)

When address data in EEPROM is corrupted, this bit is ON. If this error occurs, try to set the
slave address (BFM #27).
Buffer Memories (BFMs) Allocation 4