12. ELECTRICAL WORK
12-3. Power cable specifications
Model
PWFY-P100VM-E-BU
Model
Total
PWFY-EP100VM-E1-AU
operating
PWFY-EP100VM-E2-AU
current
Model
PAC-SV01PW-E
PWFY-P100VM-E-BU
(A)
(B)
When a solenoid valve kit is connected
Connect the solenoid valve kit TB2 and PWFY TB2.
Run the power supply wire through the access hole for power supply wire on the PWFY unit. If the hole is already
used to run other wires from the existing PWFY units, use any other wire access holes except the control wire access
hole.
PWFY-P-VM-E-AU
TB2
L N
Do not use anything other than the correct capacity breaker and fuse. Using fuse, wire or copper wire with too large ca-
pacity may cause a risk of malfunction or fire.
MEES19K013
Minimum wire thickness (mm
Main cable
branch
Ground
2.5
-
2.5
Minimum wire thickness (mm
Main cable
branch
16 A or less
1.5
1.5
25 A or less
2.5
2.5
32 A or less
4.0
4.0
Minimum wire thickness (mm
Main cable
branch
1.5
1.5
PWFY-EP100VM-E1/E2-AU
(A)
(B)
(C)
PE
PAC-SV01PW-E
TB2
L N
2
)
Breaker for
current leakage
30 A 30 mA 0.1 sec or less
2
)
Breaker for
current leakage
Ground
1.5
20A 30mA 0.1 sec. or less
2.5
30A 30mA 0.1 sec. or less
4.0
40A 30mA 0.1 sec. or less
2
)
Ground
1.5
(E)
(E)
(D)
(D)
(D)
PE
PE
PE
AIR TO WATER
Local switch (A)
Breaker for wiring
(NFB) (A)
capacity
fuse
25
25
Local switch (A)
Breaker for wiring
capacity
fuse
16
16
25
25
32
32
(A) Breaker for current leakage
(B) Local switch or breakers for wiring
(C) PWFY-P100VM-E-BU
(D) PWFY-EP100VM-E1/E2-AU
(E) Pull box
(F)
(F) PAC-SV01PW-E
30
(NFB) (A)
20
30
40
39