Specifications - Mitsubishi Electric City Multi PWFY-P100VM-E-BU Data Book

Air conditioning systems
Hide thumbs Also See for City Multi PWFY-P100VM-E-BU:
Table of Contents

Advertisement

2. SPECIFICATIONS

2. SPECIFICATIONS
Model
Power source
Heating capacity
(Nominal )
Power input
Current input
Temp. range of
for outdoor unit
heating
for heat source unit
for PWFY
Connectable
Total capacity
outdoor unit
/heat source unit
Model / Quantity
Sound pressure level (measured in anechoic room)
Diameter of
Liquid
refrigerant pipe
Gas
Diameter of
Inlet
water pipe
Outlet
Field drain pipe size
External finish
External dimension H × W × D
Net weight
Compressor
Type
Maker
Starting method
Motor output
Lubricant
Circulating water
Operation volume
Range
Protection on Internal circuit
High pressure protection
(R134a)
Inverter circuit (COMP)
Compressor
Refrigerant
Type × original charge
Control
Design pressure
R410a
R134a
Water
Drawing
External
Wiring
Document
Standard attachment
Accessory
Optional parts
Remark
Note:
*1 Nominal heating conditions (PWFY conditions are indicated in the parentheses.)
<R2-Series>
Outdoor temp. : 7°CDB/6°CWB (45°FDB / 43°FWB)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0 m (0 ft)
(Inlet water temp. 65°C
* Due to continuing improvement, the above specifications may be subject to change without notice.
* The unit is not designed for outside installations.
* Please do not use the steel material for the water piping material.
* Please always make water circulate or add the brine to the circulation water when the ambient temperature becomes 0°C or less.
* Please always make water circulate or pull out the circulation water completely when not using it.
* Please do not use ground water and well water.
MEES19K013
*1
kW
*1
kcal / h
*1
BTU / h
kW
A
W.B
-
-
dB<A>
mm(in.)
mm(in.)
mm(in.)
mm(in.)
mm(in.)
mm
in.
kg(lbs)
kW
m
/h
3
MPa
MPa
MPa
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and
other items shall be referred to the Installation Manual.
<WR2-Series>
Circulating water temp. : 20°C (68°F)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0 m (0 ft)
Water flow rate 2.15 m
/h)
(Inlet water temp. for PWFY side 65°C
3
PWFY-P100VM-E-BU
1-phase 220-230-240V 50/60Hz
12.5
10,800
42,700
2.48
11.63 - 11.12 - 10.66
-20~32°C (-4~90°F) R2-Series
10~45°C (50~113°F) WR2-Series
10~70°C (50~158°F)
50~100% of outdoor unit/heat source unit capacity
R2-Series
R2-Series (High efficiency)
WR2-Series
44
ø9.52 (ø3/8") Brazed
ø15.88 (ø5/8") Brazed
R3/4
Rc3/4
ø32 (1-1/4'')
NO
800 (785 without legs) × 450 × 300
31-1/2" (30-15/16" without legs) × 17-3/4" × 11-13/16"
59 (131)
Inverter rotary hermetic compressor
MITSUBISHI ELECTRIC CORPORATION
Inverter
1.0
NEO22
0.6~2.15
High pressure sensor, High pressure switch at 3.60 MPa (601 psi)
Over-heat protection, Over-current protection
Discharge thermo protection, Over-current protection
R134a × 1.1kg (0.50lbs)
LEV
4.15
3.60
1.00
WKB94L762
WKE94C229
Installation Manual, Instruction Book
Strainer, Heat insulation material, wire × 1 set
NONE
Water flow rate 2.15 m
/h)
3
* Install the outdoor unit (R2-Series) in an
environment where the wet bulb temp. will
not exceed 32°C.
* The water circuit must use the closed circuit.
* Please do not use it as a drinking water.
AIR TO WATER
Unit converter
BTU/h = kW × 3,412
cfm
= m
/min x 35.31
3
lbs
= kg / 0.4536
* The specification data is subject
to rounding variation.