1.Airflow based upon dry coil at 230v with factory-approved filter and electric heater (2 element heater sizes 018 through 036, 3 element heater sizes 042 through 061).
2.Airflow at 208 volts is approximately the same as 230 volts because the multi-tap ECM motor is a constant torque motor. The torque doesn't drop off at the speeds the motor operates.
3.To avoid potential for condensate blowing out of drain pan prior to making drain trap:
Return static pressure must be less than 0.40 in. wc.
Horizontal applications of 042 - 061 sizes must have supply static greater than 0.20 in. wc.
4.Airflow above 400 cfm/ton on 048-061 size could result in condensate blowing off coil or splashing out of drain pan.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Table 4 – Electric Heater Static Pressure Drop (in. wc)