Download Print this page

Siemens SIPROTEC 5 Hardware Description Manual page 26

Hide thumbs Also See for SIPROTEC 5:

Advertisement

Technical Data
6.7 Electrical Tests
Standard for Withstand Capability
or Relay Systems to Radiated Elec-
tromagnetic Interference from
Transceivers (Keying test)
IEEE Std C37.90.2
Damped oscillatory wave immunity
test
IEC 61000-4-18
Power-frequency disturbance test
at binary inputs
IEC 61000-4-16
EMC Electromagnetic Emission Tests (Type Tests, Test under Mounting Conditions)
Standards
Conducted emission on auxiliary-voltage lines
CISPR 22
Radiated emission
Loading effect in electricity-supply systems, harmonics
Harmonic current emissions
Loading effect in electricity-supply systems, voltage fluctuations
Flicker
222
20 V/m
80 MHz to 1 GHz
Pulse modulation (not valid for IO216)
100 kHz, 1 MHz, 2.5 kV (peak value)
3 MHz, 10 MHz, 30 MHz, 2 kV (peak value)
Test duration ≥ 60 s
Zone A
150 V (differential mode)
300 V (common mode)
CISPR 11
CISPR 22
IEC 60255-26 (product standard)
IEC 61000-6-4 (generic standard)
150 kHz to 30 MHz limit class A
30 MHz to 1 000 MHz limit class A
1 GHz to 6 GHz limit class A
Does not apply!
(see EN 61000-3-2, section 7,
power consumption < 75 W)
Does not apply!
(see EN 61000-3-3, section 6, no
significant voltage fluctuations)
SIPROTEC 5, Hardware Description, Manual
C53000-G5040-C002-F, Edition 06.2019