2. Central Control Devices
Up to 128 units by
individual control
AC Smart IV
Up to 64 units by
individual control
AC Ez Touch
Up to 32 units by
individual control
AC Ez
DI
DO
UI
3EA
3EA
4EA
ACP IV
AC Smart IV
• * The maximum quantity of connected indoor unit is different depending on the quantity of connected I/O
modules
• If you need more detail, please refer to the manual of product.
(http://partner.lge.com/global : Home> Download> Manuals)
Outline of system
Max.length of total transmission wiring for centralized control : 1km
Remote controller
Remote controller
Max.length of total transmission wiring for centralized control : 1km
Remote controller
Remote controller
Max.length of total transmission wiring for centralized control : 1km
Remote controller
Remote controller
ACS IO Module
ACS IO Module
DI
DO
UI
AO
AO
3EA
3EA
4EA
4EA
4EA
• Communication cable
– Types : shielding wire
– Use wires of size : over 0.75 ~ 1.5 mm
– Max. allowable temperature of cable
: 60
– Max. length of total transmission wiring
(End to End) : 1 km
• Communication cable
– Types : shielding wire
– Use wires of size : over 0.75 ~ 1.5 mm
– Max. allowable temperature of cable
: 60
– Max. length of total transmission wiring
(End to End) : 1 km
• Communication cable
– Types : shielding wire
– Use wires of size : over 0.75 ~ 1.5 mm
– Max. allowable temperature of cable
: 60
– Max. length of total transmission wiring
(End to End) : 1 km
• Communication cable
– Types : shielding wire
– Use wires of size : over 0.75 ~ 1.5 mm
– Max. allowable temperature of cable
: 60
– Max. length of total transmission wiring
(End to End) : 1 km
• Pulse cable
– Types : shielding wire
– Use wires of size : over 0.75 ~ 1.5 mm
– Max. allowable temperature of cable
: 60
– Max. length of total transmission wiring
(End to End) : 10 m
• ACP IV : Up to 16 ACS IO Modules*
• AC Smart IV : Up to 9 ACS IO Modules*
• Communication cable
– Types : shielding wire
– Use wires of size : over 0.75 ~ 1.5 mm
– Max. allowable temperature : 60°C
– Max. length of total transmission wiring
for centralized control : 1km
– Max. length of I/O wiring : 100m
Inverter 50Hz/R410A
2
2
2
2
2
2
_ 7