Ceiling Concealed Duct
1. Installation
1.4 Wiring Connection
1) Connecting cables to the Indoor Unit
Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
• Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively
Heatpump Model
Terminals on the indoor unit
Terminals on the outdoor unit
The power cord connected to the outdoor unit should be
complied with the following specifications (Rubber
insulation, type H05RN-F approved by HAR or SAA).
1 Phase(Ø)
If the supply cord is damaged, it must be replaced by a special cord or assembly availible from the manufacturer of its service agent.
Make sure that the screws of the terminal fixed tightly.

2) Clamping of cables

• Arrange 2 power cables on the control panel.
• First, fasten the clamp with a screw to the inner boss of control panel.
• For the cooling model, fix the other side of the clamp with a screw strongly.
For the heat pump model, put the 1.0 mm
clamp to the other boss of the control panel.
• In Australia, the length of power supply cord measured from the entry of the power supply cord to the middle
of live pin on the power plug should be over 1.8 m.
4 _ Inverter
50Hz/R410A
1
2
3
1
2
3
CAUTION
NORMAL CROSS-SECTIONAL AREA
2
Capacity
Phase(Ø)
Area(mm
)
30 kBtu/h
1
2.5
36 kBtu/h
1
6.0
42 kBtu/h
1
6.0
55 kBtu/h
1
6.0
2
cable(thinner cable) on the clamp and tighten it with a plastic
(220V-240V~)
1(L) 2(N)
POWER INPUT
The connecting cable connected to the indoor and outdoor
unit should be complied with the following specifications
(Rubber insulation, type H05RN-F approved by HAR or SAA).
NORMAL CROSS-SECTIONAL AREA
2
Capacity
Phase(Ø)
Area(mm
)
30 kBtu/h
1
1.0
36 kBtu/h
1
1.0
42 kBtu/h
1
1.0
55 kBtu/h
1
1.0