Inspect all wiring connections at the economizer module's termi-
nals, and verify compliance with the installation wiring diagrams.
For checkout, review the Status of each configured parameter and
perform the Checkout tests.
NOTE: For information about menu navigation and use of the
keypad see Interface Overview on page 37.
Power Up
After the W7220 module is mounted and wired, apply power.
Initial Menu Display
On initial start up, Honeywell displays on the first line and econo-
mizer W7220 on the second line. After a brief pause, the revision
of the software appears on the first line and the second line will be
blank.
Power Loss (Outage or Brownout)
All set points and advanced settings are restored after any power
loss or interruption.
NOTE: All settings are stored in non-volatile flash memory.
Status
Use the Status menu (see Table 10) to check the parameter values
for the various devices and sensors configured.
NOTE: For information about menu navigation and use of the
keypad, see Interface Overview on page 37.
Checkout Tests
Use the Checkout menu (see page 41) to test the damper operation
and any configured outputs. Only items that are configured are
shown in the Checkout menu.
NOTE: For information about menu navigation and use of the
keypad, see Interface Overview on page 37.
Fig. 60 — Single Enthalpy Curve Boundaries
Table 21 — Single Enthalpy and Dual Enthalpy High Limit Curves
TEMP.
ENTHALPY
DEWPOINT (F)
(btu/lb/da)
60
57
54
51
48
66
POINT P1
TEMP. (F)
28.0
80
26.0
75
24.0
70
22.0
65
20.0
60
32.4
86
To perform a Checkout test:
1. Scroll to the desired test in the Checkout menu using the
▲ and ▼ buttons.
2. Press the
appears.
3. Press the
pauses and then displays IN PROGRESS. When the test is
complete, DONE appears.
4. When all desired parameters have been tested, press the
(Menu Up) button to end the test.
The Checkout tests can all be performed at the time of installation
or at any time during the operation of the system as a test that the
system is operable.
Failure to follow this caution may result in damage to equip-
ment. Be sure to allow enough time for compressor startup and
shutdown between checkout tests so that you do not short-cy-
cle the compressors.

TROUBLESHOOTING

Alarms
The economizer module provides alarm messages that display on
the 2-line LCD.
NOTE: Upon power up, the module waits 60 minutes before
checking for alarms. This allows time for all the configured
devices (e.g. sensors, actuator) to become operational. The
exception is the SAT sensor which will alarm immediately.
If one or more alarms are present and there has been no keypad ac-
tivity for at least 5 minutes, the Alarms menu displays and cycles
through the active alarms.
You can also navigate to the Alarms menu at any time.
47
DUAL ENTHALPY
HIGH LIMIT
SINGLE ENTHALPY
P2 (T,RH)
P1
(T,RH)
ES4
ES2
ES5
ES3
POINT P2
HUMIDITY
TEMP. (F)
(%RH)
36.8
66.3
39.6
63.3
42.3
59.7
44.8
55.7
46.9
51.3
38.9
72.4
(Enter) button to select the item. RUN?
(Enter) button to start the test. The unit
CAUTION
ES1
HL
HUMIDITY
(%RH)
80.1
80.0
81.4
84.2
88.5
80.3

Advertisement

Table of Contents
loading

Table of Contents