ECONOMIZER HOOD ASSEMBLY

NOTE: If the power exhaust accessory is to be installed on the
unit, the hood shipped with the unit will not be used and must be
discarded. Save the aluminum filter for use in the power exhaust
hood assembly.
1. The indoor coil access panel will be used as the top of the
hood. If the panel is still attached to the unit, remove the
screws along the sides and bottom of the panel. See
Fig. 15.
2. Swing out indoor coil access panel and insert the hood
sides under the panel (hood top). Be careful not to lift the
panel too far as it might fall out. Use the screws provided
to attach the hood sides to the hood top. Use screws pro-
vided to attach the hood sides to the unit. See Fig. 16.
3. Remove the shipping tape holding the economizer baro-
metric relief damper in place.
4. Insert the hood divider between the hood sides. See
Fig. 16 and 17. Secure hood divider with 3 screws on each
hood side. The hood divider is also used as the bottom fil-
ter rack for the aluminum filter.
5. Attach the post that separates the filters with the screws
provided.
6. Open the filter clips which are located underneath the
hood top. Insert the aluminum filters into the bottom filter
rack (hood divider). Push the filter into position past the
open filter clips. Close the filter clips to lock the filters
into place. See Fig. 17.
7. Install the two rain deflectors on the edge of the hood top
as shown in Fig. 15.
8. Caulk the ends of the joint between the unit top panel and
the hood top as shown in Fig. 15.
9. Replace the filter access panel.
INDOOR
COIL
ACCESS
PANEL
Fig. 15 — Indoor Coil Access Panel Relocation
TOP
PANEL
RAIN DEFLECTORS
TOP
PANEL
CAULK
HERE
INDOOR
COIL
ACCESS
PANEL
LEFT
HOOD
SIDE
Fig. 16 — Economizer Hood Construction
DIVIDER
BAROMETRIC
RELIEF
Fig. 17 — Economizer Filter Installation
Step 9 — Install External Condensate Trap and
Line
The unit has one
/
-in. condensate drain connection on the end of
3
4
the condensate pan and an alternate connection on the bottom. See
Fig. 18. Unit airflow configuration does not determine which
drain connection to use. Either drain connection can be used with
vertical or horizontal applications.
CONDENSATE PAN (SIDE VIEW)
STANDARD
SIDE DRAIN
Fig. 18 — Condensate Drain Pan (Side View)
To use the alternate bottom drain connection, remove the red
drain plug from the bottom connection (use a
et drive extension) and install it in the side drain connection.
14
TOP
PANEL
INDOOR COIL
ACCESS PANEL
SCREW
HOOD DIVIDER
OUTSIDE
AIR
HOOD
CLEANABLE
ALUMINUM
FILTER
FILTER
ALTERNATE
DRAIN
PLUG
BOTTOM DRAIN
(FACTORY-INSTALLED)
/
-in. square sock-
1
2
FILTER
CLIP

Advertisement

Table of Contents
loading

Table of Contents