Economizer Hood Removal And Setup - Fac- Tory Option - Carrier WeatherExpert Puron 50LC 08 Series Installation Instructions Manual

Single package rooftop cooling only r-410a refrigerant
Table of Contents

Advertisement

REMOVABLE HORIZONTAL
RETURN DUCT OPENING COVER
REMOVABLE HORIZONTAL
SUPPLY DUCT OPENING COVER
Fig. 10 — Horizontal Conversion Panels
NOTCHES
BASEPAN
Fig. 11 — Location of Notches
SCREWS
BASEPAN
Fig. 12 — Horizontal Duct Panels In Place
NOTCHES
DUCT COVERS
SHEET METAL
FACE UP
13
Step 8 — Install Outside Air Hood
ECONOMIZER HOOD REMOVAL AND SETUP – FAC-
TORY OPTION
1. The hood is shipped in knock-down form and located in
the return air compartment. It is attached to the econo-
mizer using two plastic tie-wraps.
2. To gain access to the hood, remove the filter access panel.
(See Fig. 13.)
3. Locate and cut the (2) plastic tie-wraps, being careful to
not damage any wiring. (See Fig. 14.)
4. Carefully lift the hood assembly through the filter access
opening and assemble per the steps outlined in the follow-
ing procedure "Economizer Hood Assembly."
Fig. 13 — Typical Access Panel Locations
Fig. 14 — Economizer Hood Package Location
FILTER ACCESS PANEL
INDOOR COIL ACCESS PANEL
REMOVE
HOOD PARTS
CUT PLASTIC TIES
(2) PLACES
ECONOMIZER

Advertisement