4.6.5 Test and start-up

System- and communication configuring D7-SYS - SIMADYN D
Edition 03.2001
Your software is tested and commissioned in Version 3.1x using the CFC
editor which in this case, has a test mode.
in STRUC V.4.x
in D7-SYS
Start IBS G (start-up
Start the CFC editor; in the SIMATIC Manager:
program)
Double click on a CFC chart of the CPU to be tested.
Establish an online
Changeover into the CFC test mode; in CFC:
connection to the
In the creation mode, select the menu command Test >
CPUs
Test mode.
(IBS G online start)
Note: This step must be executed for each CPU which
you wish to test.
Interrupt the online
Changeover into the creation mode of the CFC; in the
connection to the
CFC:
CPUs
Select, in the test mode, the menu command Test >
(IBS G online stop)
Test mode.
Display the
In the CFC test mode:
connector values
Select the connections to be displayed or function blocks
online
and select the menu command Test > Log-on
connections.
Select the Test > Monitor menu command to display the
actual values of all these connections, logged-on with
this CPU, online.
Create the
In the CFC test mode:
interconnections
Click on the output of the function block which is to be
online
the source for the interconnection. Then click on the
input which is the destination of the connection.
Delete the
In the CFC test mode:
interconnections
Click on the function block input, which is the end of the
interconnection and then select the menu command Edit
online
> Delete.
Insert the function
In the CFC test mode:
Select the menu command View > Catalog to display
blocks online
the function block catalog of the CFC.
Select the required function block and drag it, with the
mouse key depressed, to the work area of a CFC chart.
Delete the function
In the CFC test mode:
blocks online
Remove all interconnections which go from the outputs
to the function blocks to be deleted.
Select the function block(s) to be deleted and select the
menu command Edit > Delete.
Differentiation
All online changes are permanently stored in the CFC, i.
between temporary
e. they are saved in the CPU change memory. Even
and permanent
after a CPU has been reset, the executed CPU program
online changes (IBS
and the CFC charts, which were changed online,
G OPTIONS as well
coincide.
as changing the
"permanent" option in
the dialog window
"change value").
Display the error
System diagnostics: Display the error fields of a CPU.
fields in the "Service
In the CFC:
IBS" tool
Select the menu command Target system > Module
status and then change to the register side "Error fields".
Changeover from STRUC V4.x to D7-SYS
4-31