Replacement Installation; Remove Old Thermostat; Attach Subbase To Wall - White Rodgers 1F94-80 Installation Instructions Manual

Multi-stage electronic digital thermostat
Table of Contents

Advertisement

REPLACEMENT INSTALLATION

REMOVE OLD THERMOSTAT

1. Shut off electricity at the main fuse box until installa-
tion is complete. Verify power is off with a voltmeter.
2. Remove the front cover of the old thermostat. With
wires still attached, remove wall plate from the wall.
3. If the old thermostat has a wall mounting plate,
remove the thermostat and the wall mounting plate as
an assembly.
4. Use the Cross Reference Guide to find the thermostat
type you are replacing.
5. Identify each wire attached to the old thermostat
using the labels enclosed with the new thermo-
stat. Record the identification of the wire on the
corresponding blank in Table 2.
6. Disconnect the wires from old thermostat one at a
time. Pull at least 6 inches of wire out of the wall. DO
NOT LET WIRES FALL BACK INTO THE WALL.
7. Install new thermostat using the following proce-
dures.

ATTACH SUBBASE TO WALL

1. Remove the packing material from the thermostat.
Place the fingers of one hand on the center top and
bottom portion of the thermostat. Grasp the subbase
in the other hand on the top and bottom center, and
gently pull straight out (see fig. 2). The thermostat has
pin and socket connectors. Forcing or prying on the
thermostat will cause damage to the unit.
NEW THERMOSTAT
LABEL
NUMBER
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
(13)
TABLE 1. TERMINAL REFERENCE
TERMINAL
DESIGNATION
G
Fan Output
C
Transformer 24VAC Common
L
Malfunction Light
R
Transformer 24VAC Hot
O
Changeover Output (cool)
B
Changeover Output (hot)
E1
Emergency Heat Relay (cycles on first
E2
Emergency Heat Relay (continually
Y1
Stage 1 Cool
Y2
Stage 2 Cool
W1
Stage 1 Heat (compressor)
W2
Stage 2 Heat (compressor)
A1
Damper Motor
Figure 2. Removing thermostat from subbase
TABLE 1. WIRE IDENTIFICATION LABELS
1
2
3
G
C
L
G
C
L
1
2
3
11
9
10
W1
Y1
Y2
W1
Y1
Y2
11
9
10
THIS THERMOSTAT REQUIRES BOTH THE HOT AND
COMMON SIDES OF THE 24vAC TRANSFORMER TO
BE PRESENT TO THE THERMOSTAT FOR OPERA-
TION.
FUNCTION
stage in emergency mode)
energized in emergency mode)
PULL STRAIGHT OUT
4
5
6
R
O
B
R
O
B
4
5
6
12
13
14
W2
A1
S1
W2
A1
S1
12
13
14
NOTE
OLD THERMOSTAT
TERMINAL
DESIGNATION
7
8
E1
E2
E1
E2
7
8
15
16
S2
S3
S2
S3
15
16
3

Advertisement

Table of Contents
loading