White Rodgers 1F94-80 Installation Instructions Manual

Multi-stage electronic digital thermostat

Advertisement

Quick Links

WHITE-RODGERS
Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY
BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE
PERSONAL INJURY AND/OR PROPERTY DAMAGE.
This wall-mounted, low voltage thermostat maintains
room temperature by controlling the operation of multi-
stage systems. Use this thermostat for applications re-
quiring up to two stages of heat and/or cool. Indicator
lights show the system status. The user will program two
time/temperature settings per 24 hour period. The ther-
mostat stores programs for seven independent days. The
thermostat will store both heating and cooling programs
simultaneously. A 9 volt Energizer
the stored program for approximately one week, if incom-
ing power should fail. If power failure is extensive and the
program is lost, after power restoration, the thermostat
will automatically maintain a factory preprogrammed heat-
ing temperature of 64 F or a cooling temperature of 82 F.
If in doubt about whether your wiring is millivolt, line, or low
voltage, have it inspected by a qualified heating and air
conditioning contractor, electrician, or someone familiar
with basic electricity and wiring.
Do not exceed the specification ratings.
CONTENTS
Description ......................................................... 1
Precautions ........................................................ 1
Specifications ..................................................... 2
Installation .......................................................... 2
Operation ........................................................... 5
R
®
battery will maintain
All wiring must conform to local and national electrical
codes and ordinances.
This control is a precision instrument, and should be
handled carefully. Rough handling or distorting compo-
nents could cause the control to malfunction.
Printed in U.S.A.
1F94-80
Multi-stage Electronic Digital Thermostat

INSTALLATION INSTRUCTIONS

CAUTION
!
To prevent electrical shock and/or equipment
damage, disconnect electric power to system, at
main fuse or circuit breaker box, until installation
is complete.
WARNING
!
Do not use on circuits exceeding specified volt-
age. Higher voltage will damage control and
could cause shock or fire hazard.
Do not short out terminals on gas valve or pri-
mary control to test. Short or incorrect wiring will
burn out thermostat and could cause personal
injury and/or property damage.
DESCRIPTION
PRECAUTIONS
PART NO. 37-5185A
9329

Advertisement

Table of Contents
loading

Summary of Contents for White Rodgers 1F94-80

  • Page 1: Table Of Contents

    Do not short out terminals on gas valve or pri- mary control to test. Short or incorrect wiring will burn out thermostat and could cause personal injury and/or property damage. Printed in U.S.A. 1F94-80 DESCRIPTION PRECAUTIONS CAUTION WARNING PART NO. 37-5185A...
  • Page 2: Specifications

    SPECIFICATIONS THIS CONTROL IS DESIGNED FOR USE WHERE BOTH SIDES OF THE TRANSFORMER ARE PRESENT TO THE THERMOSTAT (both the hot and common sides of the 24vAC end of the transformer.) ELECTRICAL DATA Electrical Rating: 20 to 30v AC 50/60 Hz. 0.01 to 1.5 Amps (Load per terminal) 2.5 Amps Maximum Total Load (All terminals combined)
  • Page 3: Replacement Installation

    REPLACEMENT INSTALLATION REMOVE OLD THERMOSTAT 1. Shut off electricity at the main fuse box until installa- tion is complete. Verify power is off with a voltmeter. 2. Remove the front cover of the old thermostat. With wires still attached, remove wall plate from the wall. 3.
  • Page 4 2. Connect wires beneath terminal screws on sub- base using appropriate wiring schematic (see figs. 3 through 6). 3. Place subbase over hole in wall and mark mounting hole locations on wall using subbase as a template. 4. Move subbase out of the way. Drill mounting holes. 5.
  • Page 5 IF SAFETY CIRCUITS ARE IN ONLY ONE OF THE SYSTEMS, REMOVE THE TRANSFORMER OF THE SYSTEM WITH NO SAFETY CIRCUITS. Changeover CUT AND Energized TAPE OFF! In Heat Changeover Compressor 120vAC 24vAC Energized Contactor Neutral In Cool Stage 1 TRANSFORMER HEAT PUMP SYSTEM Figure 5.
  • Page 6: Attach Thermostat To Subbase

    ATTACH THERMOSTAT TO SUBBASE WE RECOMMEND THAT YOU SET OPTION SWITCHES TO DESIRED POSITION BEFORE ATTACHING ON SUBBASE (see OPERATION). WE ALSO RECOM- MEND THAT YOU PROGRAM THE THERMOSTAT WITH BATTERY INSTALLED BEFORE ATTACHING ON SUBBASE (see OPERATION GUIDE for program- ming instructions).
  • Page 7: Check Thermostat Operation

    CHECK THERMOSTAT OPERATION FAN OPERATION 1. Turn on power to the system. If the auxiliary heat source has a standing pilot, be sure to light it. 2. Press until FAN ON is displayed. The blower SWITCH should begin to operate. 3.
  • Page 8: White-Rodgers Division Emerson Electric Co

    If you need further information about this product, please write to White-Rodgers Division, Emerson Electric Co. 9797 Reavis Road St. Louis, MO 63123-5398 Attention: Technical Service Department THIS WARRANTY STATEMENT SUPERSEDES ALL WARRANTY STATEMENTS DATED PRIOR TO OCTOBER 1, 1991. White-Rodgers Division of Emerson Electric Co.