10 Maintenance & Troubleshooting; Routine Maintenance Checks; Relay Status Verification; Meter Verification - Siemens SIMPRO-100 Instruction Manual

Motor protection relay
Table of Contents

Advertisement

SIMPRO-100
10 Maintenance & Troubleshooting
10.1
Routine Maintenance
Checks
Because the SIMPRO-100 Relay is equipped
with extensive self-tests, the most effective
maintenance task is to monitor the relay ALARM
contact. The ALARM output b-contact closes
when the relay is deenergized or when relay
self-tests fail. If you are monitoring the ALARM
contact, you know immediately if the relay is
deenergized or detects a failure. In addition, we
recommend review of relay event reports
following faults. This review frequently reveals
problems with equipment external to the relay
such as voltage transformers and control wiring.
The SIMPRO-100 Relay does not require specific
routine tests, but your operational standards may
require some periodic relay verification. If you
need or wish to perform periodic relay verification,
we recommend the following checks.
10.1.1

Relay Status Verification

Use the front-panel Status of Relay or serial port
STATUS command to verify that the relay
self-tests have not detected any out-of-tolerance
conditions.
10.1.2

Meter Verification

Verify that the relay is measuring current signals
and, if included, voltage signals by comparing the
relay meter reading to the reading of a separate
meter connected in series (for current circuits) or
parallel (for voltage circuits) with the relay input.
PRIM-2400C
Maintenance & Troubleshooting
10.1.3

Contact Input Verification

With the relay and motor off-line, short-circuit the
individual relay contact inputs using a wire jumper
or the connected switch or contact. Using the
front-panel View Relay Word\Row 9 function,
check the contact input status in the relay
front-panel display. As you short-circuit each
input, its label (IN1, IN2, IN3, etc.) should appear
in the front-panel display.
10.1.4

Contact Output Verification

Use the front-panel Pulse Out Contact\Trip
command to close the TRIP output contact.
Repeat for the other output contacts. Make sure
that each contact operates properly in its
designated annunciation, control, or tripping
circuit. See Chapter 5, page 75 and
Section 6.8.23, page 92 for more details
regarding the PULSE command.
10.2

Self-Testing

The relay runs a variety of self-tests. As shown
below, when the relay detects certain types of
self-test failures, it closes the ALARM output
b-contact. Monitoring this contact is the single
most important relay maintenance activity that
you can perform.
The relay takes the following actions for
out-of-tolerance conditions in Table 10.1 on
page 128.
10.2.1

Protection Disabled

The relay:
Disables all protection functions and
stop/start logic
Deenergizes all output contacts
Extinguishes the Relay Enabled front-panel
LED
10
127

Advertisement

Table of Contents
loading

Table of Contents