January 2020
4
Trim the transmitter
Devices are calibrated by the factory. Once installed, it is recommended to
perform a zero trim on the sensor to eliminate error due to mounting
position or static pressure effects.
This can be done by performing a zero trim via:
•
LOI – see
•
Class 2 master – see
4.1
Zero trim via Class 2 Master
Procedure
1. Place the transducer block into Out of Service (OOS) mode.
2. Apply zero pressure to device and allow to stabilize.
3. Go to Device Basic Setup → Calibration and set the Lower
Calibration Point to 0.0.
4. Place the transducer block to AUTO mode.
Quick Start Guide
Table 3-1
and
Figure 3-1
Table 3-2
for parameter configuration
Quick Start Guide
29