Laying Additional Wiring; Connecting The Power Unit; Connecting Power Cables; Figure 6-6 Shield Support - Siemens SINAMICS GL150 Operating Instructions & Installation Instructions

Medium-voltage drive
Table of Contents

Advertisement

6.11

Laying additional wiring

Keep any additional wiring in the cabinet as short as possible. Route the additional wiring tightly
against the cabinet enclosure or the mounting plates. You must twist unshielded cables
belonging to the same circuit (outgoing and return conductors).
See also
Electromagnetic compatibility (Page 77)
6.12

Connecting the power unit

6.12.1

Connecting power cables

Preconditions
You may connect the cable shields only to the transformer or the motor (away from the
converter).
Figure 6-6
Separately route back additional equipotential bonding conductors to the converter. The cross
section of this conductor must be at least as large as the total cross section of the shields.
Figure 6-7
SINAMICS GL150 6SL38503UM114PA0Z
Operating Instructions Rev.201910301420 MUSTER
Circuit breaker
Line-side transformer
Converter
Machine-side transformer
Motor
Shield support
Example: Equipotential bonding conductor
Electrical connection
6.12 Connecting the power unit
Connect shield
X
Do not connect shield
83

Advertisement

Table of Contents
loading

This manual is also suitable for:

6sl38503um114pa0z

Table of Contents