CCM Compressor control module has adjustable 30 second to 5 minute delay-on-break timer. On initial power up, or any
time the power is interrupted, the delay-on-make will be 2 minutes plus 10% of the delay-on-break setting. There is no
delay-on-make during routine operation of the unit. The module also provides the lockout feature (with 1 retry) for high
and/or low pressure controls, and a 2-minute timed bypass for low pressure control.
HPC High pressure control is auto reset. Always used with compressor control module (CCM) which is included. See Note
.
LPC
Low pressure control is auto reset. Always used with compressor control module (CCM) which is included. See Note
LAC
Low ambient control permits cooling operation down to 0°F. (Includes fan cycling control + Freeze Stat)
SK
CMC-15 is PTCR Start Kit can be used with all -A single phase models. Increases starting torque 2-3X. Not used for -B
or -C 3-phase models. Do not use if SK111 is used.
SK
SK111 Start Capacitor and Potential Relay Start Kit can be used with all -A single phase models. Increases starting
torque 9x. Not used for -B or -C 3-phase models. Do not use if CMC-15 is used.
Manual 2100-721B
Page
6 of 54

Air Conditioning Module Options

LPC
LAC
STD
Factory Installed
SK
Code
H
Field Only
Field Installed
Part
CMA-45 (WG4D Units)
CMA-46 (WG4 Units)
SK111 or CMC-15
.