Recommended W60G cooling airflow range at rated 1650 CFM @ .20 ESP (WC) is 1360 - 1850 CFM
Factory set on Rated speed for cooling and Medium speed for heating.
ESP
Inches
H
O
2
Balanced
0
1347
0.1
1272
0.2
1199
0.3
1128
0.4
1060
0.5
994
ESP
Inches
H
O
2
Balanced
0
1347
0.1
1272
0.2
1199
0.3
1128
0.4
1060
0.5
994
ESP
Inches
H
O
2
Balanced
0
1347
0.1
1272
0.2
1199
0.3
1128
0.4
1060
0.5
994
SG-5, RG-5, non-ducted application adjustment – Reduce airflow by 170 CFM for SG-5 and RG-5 installations
Manual 2100-721B
Page
50 of 54
W60G4 Indoor Blower Performance @ 230 AND 460 VOLTS
COOLING MODE
Wet Coil
Rated
High
1771
1881
1708
1823
1646
1766
1584
1709
1523
1652
1462
1596
COOLING MODE
Wet Coil
Rated
High
1771
1881
1708
1823
1646
1766
1584
1709
1523
1652
1462
1596
COOLING MODE
Wet Coil
Rated
High
1771
1881
1708
1823
1646
1766
1584
1709
1523
1652
1462
1596
TABLE 17
MANUAL FAN and HEATING MODE
125,000 BTU Input
Medium
High
1743
1682
1619
1843
1554
1783
1486
1721
1417
1657
MANUAL FAN and HEATING MODE
100,000 BTU Input
Medium
High
1743
1682
1619
1843
1554
1783
1486
1721
1417
1657
MANUAL FAN and HEATING MODE
75,000 BTU Input
Medium
High
1743
1682
1619
1843
1554
1783
1486
1721
1417
1657
113,000 BTU Input
Medium
High
1619
1554
1486
1417
1657
90,000 BTU Input
Medium
High
1682
1619
1554
1486
1721
1417
1657
68,000 BTU Input
Medium
High
1682
1619
1554
1486
1721
1417
1657