Figure 12 Low Voltage Wiring - Thermostat Using Separate Temperature And Humidity Controllers - Bard W24G4 Installation Instructions Manual

Wall mounted gas/electric
Table of Contents

Advertisement

Thermostat Using Separate Temperature and Humidity Controllers
1
Thermostat
Part #8403-057
C
(TH311DD1040)
or T4 Pro 8403-089
2
Thermostat
Part #8403-058
C
(TH522OD1151)
or T6 Pro 8403-090
UNIT LOW
C
VOLTAGE
B/W1
TERM. STRIP
FACTORY
INSTALLED
JUMPER
Electronic Humidistat
6
Bard part #
8403-047
(H200-10-21-10)
1
SET SWITCH ON THERMOSTAT TO "GAS-OIL"
CHANGE "SYSTEM TYPE", SET UP FUNCTION 1, FROM 5 (2 HEAT/ 1 COOL HEAT PUMP)
2
TO 6 (2 HEAT/ 2 COOL CONVENTIONAL).
MUST INSTALL JUMPER FOR 8407-057, 8403-058 OR OTHER THERMOSTAT THAT DOES NOT
3
HAVE OCCUPANCY OUTPUT.
4
INSTALL IF YOU REQUIRE VENTILATION ANYTIME BLOWER IS ON.
5
FACTORY INSTALLED JUMPER.
IF THIS "A" TO "G" JUMPER IS INSTALLED, YOU MUST INSURE TO REMOVE VENTILATION
6
PACKAGE ORANGE WIRE FROM TERMINAL "G".
FACTORY INSTALLED JUMPER. REMOVE TO ACTIVATE BALANCED CLIMATE™ MODE.
7
A 2-STAGE THERMOSTAT IS RECOMMENDED FOR BALANCED CLIMATE™ MODE.
FIGURE 12
Low Voltage Wiring
5
W
R
RC
5
RC Y2
W
R
W2
W2
RT
R
W3
Y2
2
5
3
4
G
Y
O/B
G
Y
Y1
A
G
1
2
3
4
6
7
YELLOW
Mechanical Humidistat
8403-038
Bard part #
(H600A 1014)
RED
THERMOSTAT SUBBASE
B
O
L
UNIT CONTROL PANEL
D
L
3
4
5
6
MIS-2788D
MIS-2788 D
Manual 2100-721B
Page
25 of 54