21. STANDARD ORIFICE SIZING AND
HIGH ALTITUDE DERATE
This furnace is shipped with fixed gas orifices for use
with natural gas and sized for 1000 BTU/cubic foot
gas. Make sure actual gas input does not exceed rating
plate input. The orifices may need to changed to get
the correct gas input. Whether they need changed
or not depends on input and the gas heat value at
standard conditions and elevation. Consult the local
gas supplier for gas heat value and any special derating
requirements. See Section 20 for more information.
At higher altitudes, the density of the air is reduced.
Therefore, for proper combustion, the quantity of gas
burned in the furnace must also be reduced. This
is called derating. This unit must be derated when
installed at altitudes greater than 6,000' above sea
level. A high altitude pressure switch must also be
installed for operation above 6,000'. High Altitude
Pressure Switch Kit number 8620-189 is designed for
this application.
W**G Rated
Sea Level
Input
41,000
40,500
39,204
45,000
45,000
43,560
61,000
60,750
58,806
68,000
67,500
65,340
75,000
75,000
72,600
81,000
81,000
78,408
90,000
90,000
87,120
100,000
100,000
96,800
113,000
112,500
108,900
125,000
125,000
121,000
Natural Gas Derate Capacities
for All Models
1000
2000
3000
37,908
36,612
42,120
40,680
56,862
54,918
63,180
61,020
70,200
67,800
75,816
73,224
84,240
81,360
93,600
90,400
105,300
101,700
117,000
113,000
It is the installer's responsibility to see that the
furnace input rate is adjusted properly. Derating
must be achieved by reducing the size of the main
burner orifices. Derating the furnace by adjusting the
manifold pressure lower than the range specified in
the Section 19, "Manifold Pressure Adjustment" is
considered to be an improper procedure.
Above 6,000' elevation orifice changes are required,
and capacity reductions are a function of altitude
impact and orifice change. Pressure switch change is
required above 6,000' elevation. For natural gas, see
Altitude Table 10 below and Orifice Tables 11A and
11B on following pages.
TABLE 10
4000
5000
6000
35,640
34,992
34,182
39,600
38,880
37,980
53,460
52,488
51,273
59,400
58,320
56,970
66,000
64,800
63,300
71,280
69,984
68,364
79,200
77,760
75,960
88,000
86,400
84,400
99,000
97,200
94,950
110,000
108,000
105,500
7000
8000
9000
33,696
33,048
32,643
37,440
36,720
36,270
50,544
49,572
48,965
56,160
55,080
54,405
62,400
61,200
60,450
67,392
66,096
65,286
74,880
73,440
72,540
83,200
81,600
80,600
93,600
91,800
90,675
104,000
102,000
100,750
Manual 2100-721B
Page
10,000
32,076
35,640
48,114
53,460
59,400
64,152
71,280
79,200
89,100
99,000
31 of 54