B-2 Reactor
B-2-1 AC Input Reactor
230V, 50/60Hz, 3-phase
kW
HP
5.5
7.5
7.5
10
11
15
15
20
18.5
25
22
30
30
40
37
50
460V, 50/60Hz, 3-phase
kW
HP
5.5
7.5
7.5
10
11
15
15
20
18.5
25
22
30
30
40
37
50
45
60
55
75
75
100
Rated Amps of AC Reactors
(A)
25
35
55
80
80
100
130
160
Rated Amps of AC Reactors
(A)
12
18
25
35
35
45
55
80
80
100
130
B-3
Appendix B Optional AccessoriesHES Series
Max. Continuous Amps
of AC Reactors (A)
37.5
52.5
82.5
120
120
150
195
240
Max. Continuous Amps
of AC Reactors (A)
3%
18
27
37.5
52.5
52.5
67.5
82.5
120
120
150
195
)
mh
Inductance (
3%
5%
Impedance
Impedance
0.5
1.2
0.4
0.8
0.25
0.5
0.2
0.4
0.2
0.4
0.15
0.3
0.1
0.2
0.075
0.15
)
mh
Inductance (
5%
Impedance
Impedance
2.5
4.2
1.5
2.5
1.2
2
0.8
1.2
0.8
1.2
0.7
1.2
0.5
0.85
0.4
0.7
0.4
0.7
0.3
0.45
0.2
0.3