Advertisement

Chapter 5 Methods of Anomaly Diagnosis

5-4 Over Voltage (ov)

Lower voltage of power
supply within the upper
limit
It's likely hybrid servo
controller breaks down or
malfunctions due to noise.
Please contact Delta for
assistance.
If you consider installing a brake unit, follow the wiring diagram below.
Slave
output/input
Terminal
Choose
"SLAVE"
SLAVE
MASTER
MASTER/SLAVE
Setting Jumper
Alarm output terminals
HES Series
OV: Over voltage
No
If the voltage of DC BUS
No
exceeds the protection value in
Adjust the brake level
and make sure it is higher
than the local voltage
Consider implementing
brake unit
CHARGE
ACT
ERR
Braking lamp
Power lamp
Fault lamp
------
480V
240V
575V
460V
230V
------
440V
220V
------
415V
210V
------
400V
200V
------
380V
190V
M1:
SLAVE output signal +
M2:
SLAVE output signal -
S1:
SLAVE input signal +
S2:
SLAVE input signal -
NOTE: Please use shielded wires
while wiring.
Check if voltage of
power supply is within
the regulated range
Yes
action
Yes
The position of the External Terminals
RB
MCM
SON RES
MO1 MO2
EMG MI3
RC
RA
5-10
DCM
+E24V
Sink/Source
Mode Switch Terminal
MI4
COM
+10V
PI
QI
AUI
MI5
AFM1
AFM
+24V
PO
SW100
V
I
ACM
ACM