Viessmann Vitocal 300-G Installation And Service Instructions Manual page 77

Table of Contents

Advertisement

Electrical connections
Plug sYS
Terminals
Function
212.2
Heating circuit pump for
heating circuit without mixer
A1
(A1)
212.3
DHW circulation pump
(cont.)
Explanation
■ This pump is installed in addition to the
secondary pump if a heating water buf-
fer cylinder is connected.
■ Connect temperature limiter as maxi-
mum temperature limiter for underfloor
heating circuit (if installed) in series
(see the following chapter)
Connection values
■ Output: 100 W
■ Voltage: 230 V~
■ Max. switching current: 4(2) A
Connect on site.
Connection values
■ Output: 50 W
■ Voltage: 230 V~
■ Max. switching current: 4(2) A
Connect on site.
Installation sequence
77