Commissioning, inspection, maintenance
Further details regarding the individual steps
External heat source
External heat source parameters
"External heat source" Ó
"Enable external heat source 7B00"
With circulation pump for DHW reheating:
"External heat source" Ó
"Enable booster heaters for DHW heating
6014"
Swimming pool water heating
Parameters for swimming pool water heating
"System definition" Ó
"External extension 7010"
"System definition" Ó
"Swimming pool 7008"
Heat pump cascade
Cascade via external extension H1
Parameter
"System definition" Ó
"System scheme 7000"
"System definition" Ó
"External extension 7010"
"System definition" Ó
"Cascade control 700A"
"System definition" Ó
"Number of lag heat pumps in
cascade 5735"
"System definition" Ó
"Output lag heat pump 700B"
"System definition" Ó
"Use of heat pump in a cas-
cade 700C"
"System definition" Ó
"Flow temperature for external
demand 730C"
116
Setting
"1"
"1"
Setting
"1"
"1"
Setting
Lead appliance
"0" to "10"
"1"
"1"
"1" to "3"
"0" to "255"
"0" to "3"
–
(cont.)
Lag heat pump
"11"
"0"
"0"
"0" to "700"
(≙ 0 to 70 °C)
–
–
–